8 Applied Settings
8 - 24
High-function General-purpose Inverter RX2 Series User’s Manual
Minimum operation time from start to sleep [AH-91] and minimum retaining time of the sleep status
[AH-92] can be set.
PID sleep operation can prevent the operation of switching between the sleep status and operation sta-
tus frequently.
PID1 to PID4 controls operate independently.
Switching PID1 to 4 by terminal enables the use for switching batch control, etc.
In PID2, selecting PID1 output to target value enables control in consideration of influences from the 2
systems.
Sleep Function Disable Time
8-1-5
PID2/PID3/PID4 Control
Feedback value
Sleep start level [AH-86]
PID target value + boost amount
[AH-90]
PID target value
Wake start level [AH-84]
Output frequency
Sleep
operation
time
[AH-87]
Wake operation
time
[AH-95]
Before sleep Minimum
operation time
[AH-91]
Sleep status Minimum
retaining time
[AH-92]