8 Applied Settings
8 - 34
High-function General-purpose Inverter RX2 Series User’s Manual
Parameter
Output Signal Function
Output terminal signal will be turned OFF when each PID feedback reaches beyond respective PID set
ranges.
Precautions for Correct Use
• Set PID1 feedback to be OFF level ≥ ON level. OFF operation will be prioritized when it is set
to Off level
ON level.
• Setting ON level/OFF level to be other than 0.00 starts outputting of a feedback comparison
signal.
Item
Terminal
name
Data
Description
Default
data
PID1 Deviation over
level
[AH-72]
0.00 to
100.00(%)
045 [OD] signal output judgment level
3.00
PID2 Deviation over
level
[AJ-17]
0.00 to
100.00(%)
047 [OD2] signal output judgment level
PID3 Deviation over
level
[AJ-37]
0.00 to
100.00(%)
089 [OD3] signal output judgment level
PID4 Deviation over
level
[AJ-57]
0.00 to
100.00(%)
091 [OD4] signal output judgment level
Item
Terminal name
Data
Description
PID1 deviation exces-
sive signal
OD
045
Signal will be turned ON when the difference
between PID target value and feedback value
exceeds the range of PID1 deviation excessive level.
PID2 deviation exces-
sive signal
OD2
047
Signal will be turned ON when the difference
between PID target value and feedback value
exceeds the range of PID2 deviation excessive level.
PID3 deviation exces-
sive signal
OD3
089
Signal will be turned ON when the difference
between PID target value and feedback value
exceeds the range of PID3 deviation excessive level.
PID4 deviation exces-
sive signal
OD4
091
Signal will be turned ON when the difference
between PID target value and feedback value
exceeds the range of PID4 deviation excessive level.
PID Feedback Comparison Signal (FBV)
0%
FBV1/FBV2/FBV3/FBV4
ON
ON
ON
PID feedback (%)
PID1 feedback/
PID2 feedback/
PID3 feedback/
PID4 feedback
Operation command
Time (s)
OFF level
[AH-73]/[AJ-18]/[AJ-38]/[AJ-58]
ON level
[AH-74]/[AJ-19]/[AJ-39]/[AJ-59]
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...