8 - 37
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-1
P
ID Con
trol
8
8-1
-7 PID U
nit C
hange
Adjustment Example
(Adjustment example 1) If you want to display 0 to 10V (0 to 100%) as 0.1 to 0.5kPa in [db-30] when
the voltage is feed-backed to the analog input 1 [Ai1]
Unit [AH-03] = 56 (kPa), decimal point position [AH-06] = 02, zero point [AH-04] = 10, end point
[AH-05] = 50
(Adjustment example 2) If you want to display -10 to 10V (-100 to 100%) as 0.1 to 0.5kPa in [db-30]
when the voltage is feed-backed to the analog input 3 [Ai3]
Unit [AH-03] = 56 (kPa), decimal point position [AH-06] = 02, zero point [AH-04] = 30, end point
[AH-05] = 50
0V
10V
0.1
0.5
Display
description
[Ai1] input
0V
10V
0.1
0.5
0.3
-10V
Display
description
[Ai3] input
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......