8 - 41
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-
2 T
riple
ss Fu
nct
ions
8
8-2
-1 Ove
rlo
ad Li
mit Level Function
Using [bA122] to [bA124] of overload limit 1 and [bA126] to [bA128] of overload limit 2, you can set
two types of overload limit functions.
You can switch between overload limit 1 and overload limit 2 with the input terminal function
038[OLR].
Turning on the [OLR] enables the overload limit 2.
[bA123]
[bA124]
IM:[Hb105]
SM(PMM):[Hd105]
Output Current
Max. Frequency
Inverter
Output
Frequency
Overload Limit Level
Deceleration set with
overload limit constant
Command
Frequency
[bA124]
IM:[Hb105]
SM(PMM):[Hd105]
OLR
ON
[bA127]
[bA123] Overload Limit 1 Level
Output Current
Command
Frequency
Inverter
Output Frequency
Max. Frequency
[bA126] Overload Limit 2 Level