8 - 43
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-
2 T
riple
ss Fu
nct
ions
8
8-2
-2 Ove
rcurren
t Suppression Selection
Parameter
Item
Parameter
Data
Description
Default
data
Over current suppress
enable, 1st-motor
[bA120]
00
Disabled
1
01
Enabled (Overcurrent suppression is acti-
vated.)
Over current suppress
Level, 1st-motor
[bA121]
Inverter rated
current
× (0.0 to 2.0)
*1
*1. On the parameter about the current and the voltage, the figures and the units to be handled vary in the setting
path.
1) Operator or CX-Drive: 0.1 A or 0.1 V (When CX-Drive is operated, set [CF-11] Resister data selection to 00
(A,V). When the data of [CF-11] Resister data selection is not set to 00 (A,V), it is not set or displayed correctly.)
2) Modbus: The current and the voltage vary, depending on the setting of Resister data selection [CF-11].
When [CF-11] Resister data selection is set to 00 (A,V), 0.1 A, 0.1 V
When [CF-11] Resister data selection is set to 01 (%), 0.01% (Rated ratio)
3) Drive programming: 0.01% (Rated ratio)
Sets the operation level of the overcurrent
suppression function.
1.8×
Inverter
rated
current
OC-supress level of
Active frequency
matching
[bb-46]
Inverter rated
current
× (0.0 to 2.0)
*1
Sets the operation level of the overcurrent
suppression function when activated with
frequency pull-in.
*2
*2. See
on page 7-69 for details.
1.0×
Inverter
rated
current
Output Current
Desired
Overcurrent
suppression
level bA121
Output Frequency
Actual acceleration after
overcurrent suppression
operation
Time
Time
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......