8 - 57
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-
2 T
riple
ss Fu
nct
ions
8
8-2
-6 Restar
t during Power
Interr
uption/Under
voltage
(Ex.3) When [bb-20] ≠00 and [bb-24] = 01, it restarts by picking up the frequency.
Note The motor will trip after instantaneous power failure allowable time.
7-5-3 Frequency Matching Start
on page 7-65 for details.
(Ex.4) When [bb-20] ≠00 and [bb-24] = 02, it restarts with frequency pull-in.
Note The motor will trip after instantaneous power failure allowable time.
on page 7-69 for details.
(Ex.5) When [bb-20] ≠00 and [bb-24] = 03, it restarts using the motor speed feedback.
Note The motor will trip after instantaneous power failure allowable time.
For motor speed feedback, the feedback input to the input terminals A and B, or feedback input to the
optional cassette PG option unit is required.
Control Power Supply
Instantaneous power
failure allowable time
Free Running
Motor Speed
Retry Standby
Time
Inverter
Output
Output signal
[AL]
Control Power Supply
Instantaneous power
failure allowable time
Free Running
Motor Speed
Retry Standby
Time
Inverter
Output
Output signal
[AL]
Control Power Supply
Instantaneous power
failure allowable time
Free Running
Motor Speed
Retry Standby
Time
Inverter
Output
Output signal
[AL]
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......