8 - 83
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8
-4 Co
n
tr
o
l Fu
n
ction
8
8-4
-3 Jogging Operation Fu
nction (
JG)
Parameter
This function allows you to fine-tune the position where a motor stops.
The jogging operation starts when frequency commands for the operation is set to [AG-20] the jogging
frequency and the [JG] terminal is turned ON.
Precautions for Correct Use
• The jogging operation is likely to cause a trip as the frequency command is outputted instan-
taneously without acceleration time. Adjust the setting value for the jogging frequency
[AG-20] to prevent the inverter trip.
• For the jogging operation, set the [AA111] operation command selection to 00, turn on the
029[JG] terminal and then put the [FW]/[RV] terminal. The operation is not allowed with the
[JG] terminal alone.
• When [AG-21] = 00, 03 for the free-running at the time of the stop, the operation settings for
free-running is required.
• When [AG-21] = 02, 05 for the DC-braking at the time of the stop, the settings for the
DC-braking function is required. Refer to
on page 7-82 respectively.
Item
Parameter
Data
Description
Default
data
Selecting the input ter-
minal
[CA-01] to
[CA-11]
035
Used for the commercial switching [CS].
-
Retry wait time before
motor restart
[bb-26]
0.3 to 100.0(s)
Set the waiting time after an operation com-
mand.
3
Restart frequency
threshold
[bb-42]
0.00 to
590.00(Hz)
Starting at 0 Hz when the detected value is
equal to or less than the set value.
0.00
8-4-3
Jogging Operation Function (JG)
[AG-20]
Output
frequency
Input signal
[JG]
Input signal
[FW]
Input signal
[RV]
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......