8 Applied Settings
8 - 90
High-function General-purpose Inverter RX2 Series User’s Manual
Once the operation command is turned off, the inverter decelerates and perform the servo lock. (4)
The servo lock is kept for the servo lock time at stop. (5)
After the brake apply delay waiting time passes, the brake release signal 037[BRK] is turned on. (6)
The operation varies depending on whether the brake check signal 037[BOK] is set to the input terminal
function.
There is a waiting for the servo lock time to pass. (7)
Setting Items Required for Brake Control2
With [BOK] setting
The inverter turns off the release signal 037[BOK], and if the 037[BOK] is not turned
off during the brake check time, the inverter trips with the [E036] brake error outputting
the fault signal 038[BER].
Without [BOK] setting
After the release signal [BRK] signal is turned off, there is a waiting for the servo lock
time at stop to pass.
Item
Parameter
Data
Description
Default
data
Brake Control Enable,
1st-motor
[AF130]
00
Disabled
00
01
Brake control 1 enabled
02
Brake control 1 enabled (forward/reverse set
individually)
03
Brake control 2 enabled
Brake open delay time,
1st-motor
[AF150]
0.00 to 2.00(s)
Set the brake release delay time.
0.20
Brake close delay
time, 1st-motor
[AF151]
0.00 to 2.00(s)
Set the brake apply delay time.
0.20
Brake answer back
check time, 1st-motor
[AF152]
0.00 to 5.00(s)
Set the time to check the brake.
0.10
Servo lock/ DC injec-
tion time at start,
1st-motor
[AF153]
0.00 to 10.00(s) Set the servo lock time at start.
0.60
Servo lock/ DC injec-
tion time at stop,
1st-motor
[AF154]
0.00 to 10.00(s) Set the servo lock time at stop.
0.60
DC braking force set-
ting, 1st-motor
[AF105]
0 to 100(%)
If the control method is neither 09: zero
speed range sensorless vector control nor
10: vector control with sensor, the DC brak-
ing is applied. Set the braking force (at the
time of stop).
30
DC braking force at
start, 1st-motor
[AF108]
0 to 100(%)
If the control method is neither 09: zero
speed range sensorless vector control nor
10: vector control with sensor, the DC brak-
ing is applied. Set the braking force (at the
time of start).
30
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......