8 Applied Settings
8 - 128
High-function General-purpose Inverter RX2 Series User’s Manual
When [CE105] = 00
When [CE105] = 01
Parameter
Item
Parameter
Data
Description
Default
data
Output terminal func-
tion selection 11-15
[CC-01] to
[CC-05]
035
036
035 [OL]: Overload prewarning signal 1 is
output.
036 [OL2]: Overload prewarning signal 2 is
output.
OFF: Less than or equal to the overload pre-
warning signal level
ON: More than or equal to the overload pre-
warning signal level
-
Relay output terminal
function selection
16A-16C
[CC-06]
-
Relay output terminal
function selection
AL1-AL0/AL2-AL0
[CC-07]
-
Over current signal
output mode selection,
1st motor
[CE105]
00
Valid in operation
01
01
Valid only in constant speed operation
Over current detection
level 1, 1st motor
[CE106]
(0.0 to 2.0) x
inverter rated
current
*1
Specify the current level at which the over-
load prewarning signal is output.
The signal will be output when the current
exceeds the overload prewarning signal
level.
1.0×
Inverter
rated
current
[FM] monitor bias
adjustment
[CE107]
1.0×
Inverter
rated
current
[CE106]
[CE107]
Overload prewarning level
Output current
Output
frequency
Output signal
[OL]
Output signal
[OL2]
[CE106]
[CE107]
Output current
Output
frequency
Output signal
[OL]
Output signal
[OL2]
Overload prewarning level
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......