8 - 141
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-7
T
erm
inal O
ut
pu
t Du
ring R
u
n
8
8-7
-2 Signal d
uring RUN
(FWR/R
V
R)
Assign the output terminal function 008 [FWR] forward-direction operating signal to one of [CC-01] to
[CC-07] that corresponds to the output terminal and output the signal.
You can output the signal only when the inverter is operating in the forward direction by assigning 008
[FWR] to the output terminal function selection.
This signal is output while the inverter performs the forward operation.
While the inverter performs the reverse operation or when stopped, this signal is not output.
The timing chart is as follows.
Assign the output terminal function 009 [RVR] reverse-direction operating signal to one of [CC-01] to
[CC-07] that corresponds to the output terminal and output the signal.
You can output the signal only when the inverter is operating in the reverse direction by assigning 009
[RVR] to the output terminal function selection.
This signal is output while the inverter performs the reverse operation.
While the inverter performs the reverse operation or when stopped, this signal is not output.
The timing chart is as follows.
Precautions for Correct Use
[FWR] and [RVR] will not be output during DC breaking or when the servo is on.
8-7-2
Signal during RUN (FWR/RVR)
Forward Run Signal (FWR)
Reverse Run Signal (RVR)
Output
Frequency
(Hz)
In
forward-direction
operation
In
reverse-direction
operation
Output signal
[FWR]
Output
Frequency
(Hz)
In
forward-direction
operation
In
reverse-direction
operation
Output signal
[RVR]
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......