8 - 143
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-7
T
erm
inal O
ut
pu
t Du
ring R
u
n
8
8-7
-4 Operation R
eady (
IRDY)
Assign the output terminal function 007 [IRDY] operation preparation completed signal to one of
[CC-01] to [CC-07] that corresponds to the output terminal and output the signal.
The operation preparation completed signal 007 [IRDY] is output when the inverter can accept opera-
tion commands.
The timing chart is as follows.
(Ex.) In the case of a terminal command
Precautions for Correct Use
• When this signal is not output, the inverter cannot be operated even if operation commands
are input.
• This signal is turned OFF in the following cases or a condition:
• During operation ready with power-ON.
• When undervoltage of the R-S-T input voltage occurs
• While the inverter has been tripped
• Under a free run stop command
Parameter
8-7-4
Operation Ready (IRDY)
Item
Parameter
Data
Description
Output terminal func-
tion selection 11-15
[CC-01] to
[CC-05]
007
[IRDY]: The operation preparation completed signal
is output to the output terminal assigned.
Relay output terminal
function selection
16A-16C
[CC-06]
Relay output terminal
function selection
AL1-AL0/AL2-AL0
[CC-07]
Reset signal input [RS]
Trip signal [AL]
Operation preparation
completed signal [IRDY]
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......