8 Applied Settings
8 - 152
High-function General-purpose Inverter RX2 Series User’s Manual
(Ex.1) Use a signal for which an AND operation has been performed with a frequency equal to or above
the set frequency (003: FA2) and a low current signal (033: LOC), and, when a current lowers after the
frequency has been determined, output the signal as Logical output 1 (LOG1) to Output terminal func-
tion 1.
• Output terminal function 1 [CC-01]: 062 (LOG1)
• Logical output signal 1 selection 1 [CC-40]: 003 (FA2)
• Logical output signal 1 selection 2 [CC-41]: 033 (LOC)
• Logical output signal 1 operator [CC-42]: 00 (AND)
(Ex.2) Use a signal for which an OR operation has been performed with an overload advance notice
signal (035: OL) and a thermal warning signal (026: THM), and, when a current falls outside the range,
output the signal as Logical output 3 (LOG3) to Output terminal function 2.
• Output terminal function 2 [CC-02]: 063 (LOG3)
• Logical output signal 3 selection 1 [CC-43]: 035 (OL)
• Logical output signal 3 selection 2 [CC-44]: 026 (THM)
• Logical output signal 3 operator [CC-45]: 01 (OR)
(Ex.3) Use a signal for which an XOR operation has been performed with an overload advance notice
signal (035: OL) and an overload advance notice signal 2 (036: OL2), and, when a current falls within a
certain range, output the signal as Logical output 5 (LOG5) to Output terminal function 3.
• Output terminal function 3 [CC-03]: 066 (LOG5)
• Logical output signal 5 selection 1 [CC-46]: 035 (OL)
• Logical output signal 5 selection 2 [CC-47]: 036 (OL2)
• Logical output signal 5 operator [CC-48]: 02 (XOR)
FA2
LOC
LOG1(AND)
ON
ON
ON
ON
ON
OL
LOC
LOG3(OR)
ON
ON
ON
ON
ON
ON
ON
OL
OL2
LOG5(XOR)
ON
ON
ON
ON
ON
ON
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......