8 - 157
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-10
Inpu
t T
ermin
al Fu
n
ct
ion
8
8-1
0-2 Inpu
t T
erminal Selections
You can set input specifications for Contact a or Contact b separately for Input terminals 1 to 9, A, and
B.
Precautions for Correct Use
Even when the “Selection of Input terminals a/b” is used, a terminal allocated with a “028 [RS]
signal” always operates as Contact a (NO).
Parameter
• Contact a: Closes with “ON,” and opens with “OFF.”
• Contact b: Closes with “OFF,” and opens with “ON.”
8-10-2 Input Terminal Selections
Item
Parameter
Data
Description
Input terminal function
selection
[CA-01] to
[CA-11]
Next item: Table
of input terminal
selections
Outputs the allocated function to the corresponding
input terminal.
Selection of Input ter-
minals a/b (NO/NC)
[CA-21] to
[CA-31]
00
Operates as Contact a (NO).
01
Operates as Contact b (NC).
Input terminal
Switching between
Contact a and Contact b
1
[CA-21]
2
[CA-22]
3
[CA-23]
4
[CA-24]
5
[CA-25]
6
[CA-26]
7
[CA-27]
8
[CA-28]
9
[CA-29]
A
[CA-30]
B
[CA-31]
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......