8 Applied Settings
8 - 158
High-function General-purpose Inverter RX2 Series User’s Manual
You can set a response time per input terminal.
This function is effective for removing noise caused by chattering, etc.
If stable terminal input is not secured due to chattering, increase the set value. However, increasing the
set value results in a slow response.
For the correspondence between input terminals and parameters, please refer to the table shown on
the below.
Parameter
(Ex.) Operation of Input terminal 1
8-10-3 Input Terminal Response Time
Input terminal
Response time
1
[CA-41]
2
[CA-42]
3
[CA-43]
4
[CA-44]
5
[CA-45]
6
[CA-46]
7
[CA-47]
8
[CA-48]
9
[CA-49]
A
[CA-50]
B
[CA-51]
Item
Parameter
Data
Description
Input terminal
response time
[CA-41]/[CA-42]/[CA-43]/[CA-44]/
[CA-45]/[CA-46]/[CC-47]/[CA-48]/
[CA-49]/[CA-50]/[CA-51]
0 to 400(ms)
*1
*1. When setting to 0, the operation starts about at 1 ms.
Sets a response time.
[CA-41]
[CA-41]
ON
OFF
OFF
ON
Operation of
input terminal
Operation of
internal function
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......