8 Applied Settings
8 - 164
High-function General-purpose Inverter RX2 Series User’s Manual
The following table is a relation between Analog Input Ai2 and Frequency Command.
Relation between Analog Input Ai2 and Frequency Command
Item
Parameter
Data
Description
Default
data
Filter time constant of
Terminal [Ai2]
[Cb-11]
1 to 500(ms)
Filters the input.
16
Start value of Terminal
[Ai2]
[Cb-13]
0.00
to 100.00(%)
Sets a frequency instruction ratio when set-
ting a start ratio for analog input.
0.00
End value of Terminal
[Ai2]
[Cb-14]
0.00
to 100.00(%)
Sets a frequency instruction ratio when set-
ting an end ratio for analog input.
100.00
Start rate of Terminal
[Ai2]
[Cb-15]
0.0
to [Cb-16](%)
With respect to a minimum ratio for analog
input for 0 to 10 V/0 to 20 mA, sets a start
ratio.
20.0
End rate of Terminal
[Ai2]
[Cb-16]
[Cb-17]
to 100.0(%)
With respect to an external frequency
instruction for 0 to 10 V, 0 to 20 mA, sets an
end ratio.
100.0
Start point selection of
Terminal [Ai2]
[Cb-17]
00
For an instruction for a value of one of
0.00% to the “Start amount [Cb-13]” and to
the “End amount [Cb-14],” whichever is
lower, one of the values of the “Start amount
[Cb-13]” and the “End amount [Cb-14],”
whichever is lower, is output.
01
01
For an instruction for a value of one of
0.00% to the “Start amount [Cb-13]” and to
the “End amount [Cb-14],” whichever is
lower, a value of 0.00% is output.
[Cb-04]
[Cb-03]
0
[Cb-06]
[Cb-05]
100
(0V/0mA)
(10V/20mA)
(V/ mA)
[Cb-03]
[Cb-04]
0
[Cb-05]
[Cb-06]
100
(0V/0mA)
(10V/20mA)
(V/ mA)
[Cb-04]
[Cb-03]
0
[Cb-05] [Cb-06] 100
(0V/0mA)
(10V/20mA)
(V/ mA)
[Cb-04]
[Cb-03]
0
[Cb-05] [Cb-06]
100
(0V/0mA)
(10V/20mA)
(V/ mA)
(Ex.1-1) [Cb-07]=00
(Ex.2-1) [Cb-07]=01
(Ex.1-2) [Cb-07]=00
(Ex.2-2) [Cb-07]=01
Maximum
frequency
The output frequency
for 0% to [Cb-05] is
[Cb-03].
Analog input
The output frequency
for [Cb-06] to 100% is
[Cb-04].
The output frequency
for 0% to [Cb-05] is 0
Hz.
The output frequency
for [Cb-06] to 100% is 0
Hz.
Analog input
Analog input
Analog input
Maximum
frequency
Maximum
frequency
Maximum
frequency
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......