8 Applied Settings
8 - 168
High-function General-purpose Inverter RX2 Series User’s Manual
Precautions for Correct Use
• The maximum input pulse in the phase coefficient monitoring mode becomes a maximum of
32 kpps. (When the duty ratio is approximately 50%)
• An accumulation counter value cannot be stored. After the power supply is turned on, the
value becomes zero.
• The maximum input pulse in the terminal input monitoring mode depends on the settings of
the input terminal response functions [CA-41] to [CA-51].
Parameter
Monitors whether the input terminal functions [PLA] and [PLB] are turned on.
Item
Parameter
Data
Description
Default
data
Input terminal function
[CA-01] to
[CA-11]
103
[PLA]: Accepts a pulse input.
-
104
[PLB]: Accepts a pulse input.
097
[PCC]: Clears the integrated value.
Output terminal func-
tion
[CC-01] to
[CC-07]
091
[PCMP]: Outputs pulse compare-match sig-
nals.
-
Pulse train detection
object selection
[CA-90]
00
Disabled
00
01
Frequency command
02
Speed feedback
03
Pulse count
Mode selection of
pulse train input
[CA-91]
00
90° phase difference
00
01
forward/reverse rotation command and rota-
tion direction
02
forward/reverse rotation pulse string
Comparing match out-
put ON-level for Pulse
count
[CA-97]
0 to 65535
When the number of pulses reaches this set
value, Turn on [PCMP].
0
Comparing match out-
put OFF-level for
Pulse count
[CA-98]
0 to 65535
When the number of pulses reaches this set
value, Turn off [PCMP].
0
Comparing match out-
put Maximum value for
Pulse count
[CA-99]
0 to 65535
A one-shot pulse can be achieved when the
value is 0.
When the number of pulses reaches the set
value, the internal counter is cleared.
0
Pulse counter monitor
[dA-28]
0 to
2147483647
Displays the counter integrated value.
-
Terminal Input Monitoring Mode
Normal rotation
pulse string input
Number of detected pulses
Terminal
[PLA]
Reverse rotation
pulse string input
Terminal
[PLB]
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......