2 Design
2 - 4
High-function General-purpose Inverter RX2 Series User’s Manual
2-1
Installation
Mount the 3G3RX2 Series Inverter vertically on a wall withstanding the weight and vibration with
screws.
Not installing the product vertically on the wall may cause loosing cooling capacity and cause trips and
damages.
For the mounting dimensions, refer to
When you use 3G3RX2-A2110 at Low Duty (LD) / Very Low Duty (VLD) or 3G3RX2-A2220 at Very Low
Duty (VLD), you must attach the main body on the wall in a special way as shown the instruction below.
Mounting of 3G3RX2-A2110:
1
Unscrew the four screws temporarily fixing the mounting fittings (top and bottom) as factory
shipping
2
Pull and slide the fittings (top and bottom) to match the next hole on the fittings to the screw
holes on the main body.
3
Fix the fittings on the main body by the four screws you removed at step 1. (Torque: 2.2 to 2.5
N·m)
4
Fix the main body on the wall with four other screws you provide.
2-1-1
Inverter Installation
2-1-2
Precaution for Installation
Screw
Screw
Screw
Screw
No Gradient
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......