8 Applied Settings
8 - 182
High-function General-purpose Inverter RX2 Series User’s Manual
You can bias Point 0 as shown in the below figure.
(Ex.) Outputting information on the “[dA-01] output frequency monitor” to [Ao1] in a voltage range from
0 to 10 V
Output in a range from 0 Hz to the maximum frequency (60 Hz).
[Cd-23]=0.0%, [Cd-24]=100.0%
(Ex.) Outputting information on the output frequency monitor to [Ao1] in a current range from 4 to 20 mA
Output in a range from 0 Hz to the maximum frequency (50 Hz).
[Cd-23]=20.0%, [Cd-24]=80.0%
Bias Adjustment of Analog Output
Terminal
Current/voltage
Bias parameter
Ao1
Common to voltage/current
[Cd-23]
Ao2
Common to voltage/current
[Cd-33]
(V):(mA)
10 :20
0: 0
0
5:10
-5: -10
Output scale
Outputting will
be made in this
range.
Maximum
Parallel
movement
[Bias]=-50.0(%)
[Bias]=0.0(%)
[Bias]=50.0(%)
(V)
10
0
60Hz
0Hz
5
30Hz
Maximum frequency
Output frequency (Hz)
(mA)
20
0
50Hz
0Hz
10
25Hz
[Cd-23]=20.0(%)
4
[Cd -24 ]=8 0.0 (%)
Maximum frequency
Output frequency (Hz)
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......