8 Applied Settings
8 - 186
High-function General-purpose Inverter RX2 Series User’s Manual
Parameter
When selecting the output monitor, set the registered number of each code. For example, when
using dA-02 of output current monitor via [FM] output terminal, set “10002(2712h)” to [Cd-03].
With the “Bias adjustment [Cd-13]” of the “PWM output,” you can bias Point 0 as shown in the below fig-
ure.
Item
Parameter
Data
Description
Default
data
[FM] monitor output
wave form selection
[Cd-01]
00
PWM output (Frequency: 6.4 ms)
00
01
Digital frequency output
[FM] monitor output
base frequency (at
PWM output)
[Cd-02]
0 to 3600[Hz]
[FM] terminal output frequency in the full
scale.
2880
[FM] monitor output
selection
[Cd-03]
Parameter number
for
Sets a parameter number.
[dA-01]
Analog monitor adjust
mode enable
[Cd-10]
00
Invalid.
00
01
Valid. Outputs to terminals output levels
in the adjustment mode.
Filter time constant of
[FM] monitor
[Cd-11]
1 to 500[ms]
Filters FM output data.
100
[FM] Data type
selection
[Cd-12]
00
Outputs the absolute value of data.
00
01
Outputs data with a symbol.
[FM] monitor bias
adjustment
[Cd-13]
-100.0 to 100.0[%] Biases data to adjust Point 0 of data.
0.0
[FM] monitor gain
adjustment
[Cd-14]
-1000.0 to
1000.0[%]
Apply a gain to data to adjust an inclina-
tion in data.
100.0
Output level setting at
[FM] monitor adjust
mode
[Cd-15]
-100.0 to 100.0[%]
Sets output in the adjustment mode. It
selects the maximum output (at 100.0%),
the minimum output (at 0.0%)
([Cd-12]=00), or the minimum output (at
-100.0%) ([Cd-12]=01).
100.0
[Cd-01] [FM] Terminal Output Form Selection is Set to 00
t/T(%)
10 0
0
[Cd -13]=50.0(%)
[Cd -13]= -50.0(%)
[Cd -13]=0.0(%)
0
50
-50
Output scale
Outputting will
be made in this
range.
Maximum
Parallel
movement
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......