9 Communications Functions
9 - 8
High-function General-purpose Inverter RX2 Series User’s Manual
<Abnormal Response>
Field Configuration
• If an error (except for a communications error) is found in the query content, the inverter will return an
exception response without performing any operation.
• For the cause of an error, check the function code for the response. The function code for an excep-
tion response is the sum of the function code for the query and 80 hex.
• For the cause of an error, check the exceptional code.
Exception code
23h The writing function code is used in read-only function parameter.
26h While data is being written into the inverter, or the inverter's data is being initialized, some data is
written into the inverter.
27h There was an access to only the higher side register of 2 register long parameter.
<No Response>
The inverter will ignore the query and send back no response if:
• It receives a broadcast query.
• It detects a communications error in receiving a query.
• The slave address specified in a query does not match the inverter’s slave address setting.
• The length of the time interval set for the inverter to receive the next data of the message after receiv-
ing a message is less than 3.5 characters.
• The data length of a query is inappropriate.
• The length of the reception interval in a frame exceeds the 1.5 characters.
• The error check code specified in a query does not match (CRC error).
• When it received query of slave address 250 to 254
Note Provide a timer on the master side for monitoring the response and set it to resend the same query if no
response is received within the set time.
Slave address
Function code
Exception code
CRC-16
Code
Description
01 hex
An unsupported function is specified.
02 hex
The specified address does not exist.
03 hex
The specified data is in an unacceptable format.
21 hex
Writing to a holding register is specified, but the data is out of the range allowed for the inverter.
22 hex
The inverter does not allow this function because:
• Inverter is in an operation busy state.
• Function attempts to change a register that cannot be changed during RUN.
• Function attempts to issue the Enter command during RUN (in an undervoltage state).
• Function attempts to write data to a register during trip (in an undervoltage state).
• Function attempts to write data to a read-only register (coil).
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......