9 Communications Functions
9 - 10
High-function General-purpose Inverter RX2 Series User’s Manual
Query
Response
*1. Broadcasting cannot be performed.
*2. Note that the coil start number is 0004, which is 1 less than the coil number 0005.
*3. If the number of coils to be read is set to 0 or more than 32, an error code (03 hex) will be returned.
*4. Data as much as the number of data bytes will be transferred.
Data received to a response shows status of coil No. 0007h to 000Eh (Input terminal 1 to 8).
Therefore, the received data “17 hex = 00010111 binary” can be read from the LSB that shows the sta-
tus of coil number 0007 hex, as follows:
If, in the last coil data, the read coil exceeds the defined coil range, such out-of-range coil data will be
transferred as 0.
If the Read Coil Status function is not executed normally, refer to
No.
Field name
Example [hex]
Remarks
1
Slave address
*1
08
2
Function code
01
3
Coil start number (MSB)
*2
00
(Coil address) = (Coil number) – 1
4
Coil start number (LSB)
*2
04
5
Number of coils (MSB)
*3
00
6
Number of coils (LSB)
*3
06
7
CRC-16 (MSB)
5C
8
CRC-16 (LSB)
90
No.
Field name
Example [hex]
Remarks
1
Slave address
08
2
Function code
01
3
Number of data bytes
01
4
Coil data
*4
17
17 hex = 0 0 0 1 0 1 1 1
Input terminal 6 Input terminal 1
5
CRC-16 (MSB)
12
6
CRC-16 (LSB)
1A
Coil No.
00Fh
00Eh
00Dh
00Ch
00Bh
00Ah
009h
008h
007h
006h
005h
Coil Status
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
ON
Input Terminal No. B
A
9
8
7
6
5
4
3
2
1
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......