9 Communications Functions
9 - 12
High-function General-purpose Inverter RX2 Series User’s Manual
Writes the ON/OFF status to a single coil. The coil status changes as shown in the table below.
Example
To issue the RUN command to the inverter with slave address 10.
To operate the inverter, you need to set AA111 to 03. Write the RUN command to the coil number 0001.
Query
Response
*1. During a broadcast, no response will be sent back.
*2. Note that the coil start number is 0000, which is 1 less than the coil number 0001.
If the Write to Coil function is not executed normally, refer to
Write to Coil [05 hex]
Data
Coil status
OFF to ON
ON to OFF
Written data (MSB)
FF hex
00 hex
Written data (LSB)
00 hex
00 hex
No.
Field name
Example [hex]
Remarks
1
Slave address
*1
0A
2
Function code
05
3
Coil start number (MSB)
*2
00
(Coil address) = (Coil number) – 1
4
Coil start number (LSB)
*2
00
5
Written data (MSB)
FF
OFF to ON: FF00 hex
6
Written data (LSB)
00
7
CRC-16 (MSB)
8D
8
CRC-16 (LSB)
41
No.
Field name
Example [hex]
1
Slave address
0A
2
Function code
05
3
Coil start number (MSB)
00
4
Coil start number (LSB)
00
5
Written data (MSB)
FF
6
Written data (LSB)
00
7
CRC-16 (MSB)
8D
8
CRC-16 (LSB)
41
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......