9 - 15
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-
3 Explan
atio
n
o
f Each
Fun
ctio
n C
ode
9
Rewrites the ON/OFF status to consecutive multiple coils.
Precautions for Correct Use
Precautions for Correct Use
The byte order was changed when data over 1 byte is processed with writing function of sev-
eral coils via Modbus. In addition, due to the specifications of Modbus communication, the
inverter cannot process any odd number of bytes.
If the data to be written has an odd number of bytes, add 1 byte of padding data.
Send data in the data layout for an even number of bytes as shown below, according to the
number of data bytes to be written.
• Data sent as 1-byte data (1 to 8 coils)
• Data sent as 2-byte data (9 to 16 coils)
• Data sent as 3-byte data (17 to 24 coils)
• Data sent as 4-byte data (25 to 32 coils)
Note, however, that this Inverter does not send data of 2 bytes or more because it can write to
coil numbers 0001 hex to 000F hex.
Example
Change Inverter’s input terminals 1 to 6 for slave address 5.
Change input terminals into statuses shown below table.
Write to Multiple Coils [0F hex]
Coil 8 to Coil 1
(Padding data)
Coil 8 to Coil 1
Coil 16 to Coil 9
Coil 8 to Coil 1
Coil 16 to Coil 9
Coil 24 to Coil 17
(Padding data)
Coil 8 to Coil 1
Coil 16 to Coil 9
Coil 24 to Coil 17
Coil 32 to Coil 25
Item
Data
Multi-function input terminal
1
2
3
4
5
6
Coil number
0005 hex
0006 hex
0007 hex
0008 hex
0009 hex
000A hex
Terminal status
ON
ON
ON
OFF
ON
OFF
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......