2 Design
High-function General-purpose Inverter RX2 Series User’s Manual
2-1
Installatio
n
2
2-
1-3 I
nstallation
E
n
vironmen
t
For the calculation of heat radiation from a cabinet, the following table shows the amount of heat gener-
ation (loss) according to the inverter capacity.
Loss according to the Inverter Capacity
Voltage
Loss at 100% load (W)
200V
400V
ND
LD
VLD
ND
LD
VLD
0.4
50
53
65
0.75
65
80
105
62
67
76
1.5
93
118
135
94
98
104
2.2
142
162
197
96
107
134
3.7
225
253
314
145
163
189
5.5
348
365
420
235
260
290
7.5
376
400
520
240
280
306
11
498
625
754
260
306
380
15
742
922
1059
361
444
482
18.5
964
1167
1332
495
601
633
22
1163
1263
1377
687
805
860
30
1317
1536
1698
783
854
920
37
1534
1801
2092
812
880
971
45
1625
1940
2300
1047
1218
1300
55
1878
2669
3046
1130
1488
1592
75
1570
1811
2020
90
2034
2150
2359
110
2219
2397
2557
132
3872
4352
4598
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......