9 - 51
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-
5 Mod
bu
s Com
m
u
n
icat
ion
Regi
ster Nu
m
b
er
List
9
9-5-
4 Group
A
Register
List
30D5h
30D4h
DC braking selection,
1st-motor
AF101
R/W
00: Disabled
01: Enabled
02: Frequency command
-
30D6h
30D5h
Braking type selection,
1st-motor
AF102
R/W
00: DC braking
01: Speed servo lock
02: Position servo lock
-
30D7h
30D6h
DC braking frequency,
1st-motor
AF103
R/W
0 to 59000
0.01(Hz)
30D8h
30D7h
DC braking delay time,
1st-motor
AF104
R/W
0 to 500
0.01(s)
30D9h
30D8h
DC braking force setting,
1st-motor
AF105
R/W
0 to 100
1(%)
30Dah
30D9h
DC braking active time at
stop, 1st-motor
AF106
R/W
0 to 6000
0.01(s)
30DBh
30DAh
DC braking operation method
selection, 1st-motor
AF107
R/W
00: Edge mode
01: Level mode
-
30DCh
30DBh
DC braking force at start,
1st-motor
AF108
R/W
0 to 100
1(%)
30DDh
30DCh
DC braking active time at
start, 1st-motor
AF109
R/W
0 to 6000
0.01(s)
30E8h
30E7h
ContactorControl Enable,
1st-motor
AF120
R/W
00: Disabled
01: Enabled: primary side
02: Enabled: secondary side
-
30E9h
30E8h
Run delay time, 1st-motor
AF121
R/W
0 to 200
0.01(s)
30Eah
30E9h
Contactor off delay time,
1st-motor
AF122
R/W
0 to 200
0.01(s)
30Ebh
30Eah
Contactor answer back check
time, 1st-motor
AF123
R/W
0 to 500
0.01(s)
30F2h
30F1h
Brake Control Enable,
1st-motor
AF130
R/W
00: Disabled
01: Brake control 1 common in
forward/reverse rotation
02: Brake control 1 for-
ward/reverse set individually
03: Brake control 2
-
30F3h
30F2h
Brake Wait Time for Release,
1st-motor (Forward side)
AF131
R/W
0 to 500
0.01(s)
30F4h
30F3h
Brake Wait Time for Accel.,
1st-motor (Forward side)
AF132
R/W
0 to 500
0.01(s)
30F5h
30F4h
Brake Wait Time for Stopping,
1st-motor (Forward side)
AF133
R/W
0 to 500
0.01(s)
30F6h
30F5h
Brake Wait Time for Confir-
mation, 1st-motor (Forward
side)
AF134
R/W
0 to 500
0.01(s)
30F7h
30F6h
Brake Release Frequency
Setting, 1st-motor (Forward
side)
AF135
R/W
0 to 59000
0.01(Hz)
30F8h
30F7h
Brake Release Current Set-
ting, 1st-motor (Forward side)
AF136
R/W
(0.0 to 2.0)
× Inverter rated current
*3
0.1(A)
30F9h
30F8h
Braking Frequency, 1st-motor
(Forward side)
AF137
R/W
0 to 59000
0.01(Hz)
30Fah
30F9h
Brake Wait Time for Release,
1st-motor (Reverse side)
AF138
R/W
0 to 500
0.01(s)
30FBh
30FAh
Brake Wait Time for Accel.,
1st-motor (Reverse side)
AF139
R/W
0 to 500
0.01(s)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......