9 Communications Functions
9 - 52
High-function General-purpose Inverter RX2 Series User’s Manual
30FCh
30FBh
Brake Wait Time for Stopping,
1st-motor (Reverse side)
AF140
R/W
0 to 500
0.01(s)
30FDh
30FCh
Brake Wait Time for Confir-
mation, 1st-motor (Reverse
side)
AF141
R/W
0 to 500
0.01(s)
30Feh
30FDh
Brake Release Frequency
Setting, 1st-motor (Reverse
side)
AF142
R/W
0 to 59000
0.01(Hz)
30FFh
30FEh
Brake Release Current Set-
ting, 1st-motor (Reverse side)
AF143
R/W
(0.0 to 2.0)
× Inverter rated current
*3
0.1(A)
3100h
30FFh
Braking Frequency, 1st-motor
(Reverse side)
AF144
R/W
0 to 59000
0.01(Hz)
3106h
3105h
Brake open delay time,
1st-motor
AF150
R/W
0 to 200
0.01(s)
3107h
3106h
Brake close delay time,
1st-motor
AF151
R/W
0 to 200
0.01(s)
3108h
3107h
Brake answer back check
time, 1st-motor
AF152
R/W
0 to 500
0.01(s)
3109h
3108h
Servo lock/ DC injection time
at start, 1st-motor
AF153
R/W
0 to 1000
0.01(s)
310Ah
3109h
Servo lock/ DC injection time
at stop, 1st-motor
AF154
R/W
0 to 1000
0.01(s)
3139h
3138h
Jump frequency 1, 1st-motor
AG101
R/W
0 to 59000
0.01(Hz)
313Ah
3139h
Jump frequency width 1,
1st-motor
AG102
R/W
0 to 1000
0.01(Hz)
313Bh
313Ah
Jump frequency 2, 1st-motor
AG103
R/W
0 to 59000
0.01(Hz)
313Ch
313Bh
Jump frequency width 2,
1st-motor
AG104
R/W
0 to 1000
0.01(Hz)
313Dh
313Ch
Jump frequency 3, 1st-motor
AG105
R/W
0 to 59000
0.01(Hz)
313Eh
313Dh
Jump frequency width 3,
1st-motor
AG106
R/W
0 to 1000
0.01(Hz)
3142h
3141h
Acceleration stop frequency
setting, 1st-motor
AG110
R/W
0 to 59000
0.01(Hz)
3143h
3142h
Acceleration stop time setting,
1st-motor
AG111
R/W
0 to 600
0.1(s)
3144h
3143h
Deceleration stop frequency
setting, 1st-motor
AG112
R/W
0 to 59000
0.01(Hz)
3145h
3144h
Deceleration stop time set-
ting, 1st-motor
AG113
R/W
0 to 600
0.1(s)
314Ch
314Bh
Jogging frequency
AG-20
R/W
0 to 1000
0.01(Hz)
314Dh
314Ch
Jogging stop mode selection
AG-21
R/W
00: Disabled during FRS opera-
tion at stop
01: Disabled during deceleration
stop operation
02: Disabled during DB operation
at stop
03: Enabled during FRS opera-
tion at stop
04: Enabled during deceleration
stop operation
05: Enabled during DB operation
at stop
-
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......