9 Communications Functions
9 - 60
High-function General-purpose Inverter RX2 Series User’s Manual
3221h
3220h
PID3 proportional gain
AJ-33
R/W
0 to 1000
0.1
3222h
3221h
PID3 integral time constant
AJ-34
R/W
0 to 36000
0.1(s)
3223h
3222h
PID3 derivative gain
AJ-35
R/W
0 to 10000
0.01(s)
3224h
3223h
PID3 output range
AJ-36
R/W
0 to 10000
0.01(%)
3225h
3224h
PID3 Deviation over level
AJ-37
R/W
0 to 10000
0.01(%)
3226h
3225h
PID3 Feedback compare sig-
nal turn-off level
AJ-38
R/W
0 to 10000
0.01(%)
3227h
3226h
PID3 Feedback compare sig-
nal turn-on level
AJ-39
R/W
0 to 10000
0.01(%)
3229h
3228h
PID4 enable
AJ-41
R/W
00: Disabled
01: Enabled Without reverse out-
put
02: Enabled With reverse output
1
322Ah
3229h
PID4 deviation inverse
AJ-42
R/W
00: Disabled
01: Enabled
1
322Bh
322Ah
PID4 unit selection
AJ-43
R/W
C-70 at the end of Appendices C
1
322Ch
322Bh
PID4 scale adjustment (at
0%)
AJ-44
R/W
-10000 to 10000
1
322Dh
322Ch
PID4 scale adjustment (at
100%)
AJ-45
R/W
-10000 to 10000
1
322Eh
322Dh
PID4 scale adjustment (point
position)
AJ-46
R/W
0:00000.
01:0000.0
02:000.00
03:00.000
04:0.0000
-
322Fh
322Eh
Input source selection of
Set-point for PID4
AJ-47
R/W
00: Disabled
01: Ai1 terminal input
02: Ai2 terminal input
03: Ai3 terminal input
04: (Reserved)
05: (Reserved)
06: (Reserved)
07: Parameter setting
08: RS 485
09: Option 1
10: Option 2
11: Option 3
12: Pulse string input: Inverter
13: Pulse string input: Option
-
3232h
3221h
Set-point setting for PID4
AJ-50
(HIGH)
R/W
-100.00 to 100.00
*4
Unit differs
depending
on setting
[AJ-43]
[AJ-46].
3233h
3232h
AJ-51
(LOW)
R/W
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......