9 - 67
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-
5 Mod
bu
s Com
m
u
n
icat
ion
Regi
ster Nu
m
b
er
List
9
9-5-
5 Group b
Register
List
332Dh
332Ch
Carrier speed setting,
1st-motor
bb101
R/W
[Ub-03]=02: ND
0.5 to 16.0 (kHz)
[Ub-03]=01: LD
0.5 to 12.0 (kHz)
[Ub-03]=00: VLD
0.5 to 10.0 (kHz)
*3
0.1kHz
332Eh
332Dh
Sprinkle carrier pattern
selection, 1st-motor
bb102
R/W
00: Disabled
01: Pattern 1 enabled
02: Pattern 2 enabled
03: Pattern 3 enabled
-
332Fh
332Eh
Automatic-carrier reduction
selection, 1st-motor
bb103
R/W
00: Disabled
01: Enabled: current
02: Enabled: temperature
-
3336h
3335h
Automatic error reset
selection
bb-10
R/W
00: Disabled
01: Enabled with operation com-
mand OFF
02: Enable after the setting time
-
3337h
3336h
Alarm signal selection at
Automatic error reset is active
bb-11
R/W
00: Output
01: Not output
-
3338h
3337h
Automatic error reset wait
time
bb-12
R/W
0 to 600
1(s)
3339h
3338h
Automatic error reset number
bb-13
R/W
0 to 10
1
3340h
3339h
The number of retries after
instantaneous power failure
bb-20
R/W
0 to 16 / 255
1
3341h
3340h
The number of retries after
under voltage
bb-21
R/W
0 to 16 / 255
1
3342h
3341h
The number of retries after
over current
bb-22
R/W
0 to 5
1
3343h
3342h
The number of retries after
over voltage
bb-23
R/W
0 to 5
1
3344h
3343h
Selection of restart mode
@Instantaneous power fail-
ure/ under-voltage trip
bb-24
R/W
00: 0Hz
01: (Frequency matching
02: Frequency entrainment
03: Detection speed
04: Trip after frequency matching
deceleration stop
-
3345h
3344h
Allowable under-voltage
power failure time
bb-25
R/W
3 to 250
0.1(s)
3346h
3345h
Retry wait time before motor
restart
bb-26
R/W
3 to 1000
0.1(s)
3347h
3346h
Instantaneous power fail-
ure/under-voltage trip alarm
enable
bb-27
R/W
00: Disabled
01: Enabled at stop
02: Disabled at stop and deceler-
ation stop
-
3348h
3347h
Selection of restart mode
@over-current
bb-28
R/W
00: 0Hz
01: Frequency matching
02: Frequency entrainment
03: Detection speed
04: Trip after frequency matching
deceleration stop
-
3349h
3348h
Wait time of restart
@over-current
bb-29
R/W
3 to 1000
0.1(s)
Register
No.
Modbus
register
spec. No.
Function name
Parame-
ter No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......