9 - 69
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-
5 Mod
bu
s Com
m
u
n
icat
ion
Regi
ster Nu
m
b
er
List
9
9-5-
5 Group b
Register
List
3382h
3381h
Position deviation error detec-
tion level
bb-86
R/W
0 to 65535 (×100pls)
1(×100pl
s)
3383h
3382h
Position deviation error detec-
tion time
bb-87
R/W
0 to 50
0.1(s)
33F5h
33F4h
STO input display selection
bd-01
R/W
00: With indication
01: Without indication
02: Trip
-
33F6h
33F5h
STO input change time
bd-02
R/W
0 to 6000
0.01(s)
33F7h
33F6h
Display selection at STO input
change time
bd-03
R/W
00: With indication
01: Without indication
-
33F8h
33F7h
Action selection after STO
input change time
bd-04
R/W
00: Retain only the condition
01: Disabled
02: Trip
-
59D9h
59D8h
Frequency limit selection, 2nd
motor
bA201
R/W
Same as bA101
-
59Dah
59D9h
Upper frequency limit, 2nd
motor
bA202
R/W
Same as bA102
0.01(Hz)
59DBh
59DAh
Lower frequency limit, 2nd
motor
bA203
R/W
Same as bA103
0.01(Hz)
59E2h
59E1h
Torque limit selection,
2nd-motor
bA210
R/W
Same as bA110
-
59E3h
59E2h
Torque limit parameter mode
selection, 2nd-motor
bA211
R/W
Same as bA111
-
59E4h
59E3h
Torque limit 1 (Forward driv-
ing), 2nd-motor
bA212
R/W
Same as bA112
0.1(%)
59E5h
59E4h
Torque limit 2 (Reverse
regenerative), 2nd-motor
bA213
R/W
Same as bA113
0.1(%)
59E6h
59E5h
Torque limit 3 (Reverse driv-
ing), 2nd-motor
bA214
R/W
Same as bA114
0.1(%)
59E7h
59E6h
Torque limit 4 (Forward regen-
erative), 2nd motor
bA215
R/W
Same as bA115
0.1(%)
59E8h
59E7h
Torque limit LADSTOP
selection, 2nd-motor
bA216
R/W
Same as bA116
-
59Ech
59EBh
Over current suppress
enable, 2nd-motor
bA220
R/W
Same as bA120
1
59Edh
59ECh
Over current suppress Level,
2nd-motor
bA221
R/W
Same as bA121
0.1(A)
59Eeh
59EDh
Overload restriction 1 mode
selection, 2nd-motor
bA222
R/W
Same as bA122
-
59Efh
59EEh
Overload restriction 1 active
level, 2nd-motor
bA223
R/W
Same as bA123
0.1(A)
59F0h
59EFh
Overload restriction 1 action
time, 2nd-motor
bA224
(HIGH)
R/W
Same as bA124
0.01(s)
59F1h
59F0h
bA225
(LOW)
R/W
59F2h
59F1h
Overload restriction 2 mode
selection, 2nd-motor
bA226
R/W
Same as bA126
-
59F3h
59F2h
Overload restriction 2 active
level, 2nd-motor
bA227
R/W
Same as bA127
0.1(A)
59F4h
59F3h
Overload restriction 2 action
time, 2nd-motor
bA228
(HIGH)
R/W
Same as bA128
0.01(s)
59F5h
59F4h
bA229
(LOW)
R/W
Register
No.
Modbus
register
spec. No.
Function name
Parame-
ter No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......