9 Communications Functions
9 - 70
High-function General-purpose Inverter RX2 Series User’s Manual
5A00h
59FFh
Over-voltage suppression
enable, 2nd-motor
bA240
R/W
Same as bA140
-
5A01h
5A00h
Over-voltage suppression
active level, 2nd-motor
bA241
R/W
Same as bA141
0.1(Vdc)
5A02h
5A01h
Over-voltage suppression
action time, 2nd-motor
bA242
(HIGH)
R/W
Same as bA142
0.01(s)
5A03h
5A02h
bA243
(LOW)
R/W
5A04h
5A03h
DC bus constant control pro-
portional gain, 2nd-motor
bA244
R/W
Same as bA144
0.01
5A05h
5A04h
DC bus constant control inte-
gral gain, 2nd-motor
bA245
R/W
Same as bA145
0.01(s)
5A06h
5A05h
Over magnetization function
selection, 2nd-motor
bA246
R/W
Same as bA146
-
5A07h
5A06h
Over magnetization output fil-
ter time constant, 2nd-motor
bA247
R/W
Same as bA147
0.01(s)
5A08h
5A07h
Over magnetization voltage
gain, 2nd-motor
bA248
R/W
Same as bA148
1(%)
5A09h
5A08h
Over magnetization level set-
ting, 2nd-motor
bA249
R/W
Same as bA149
0.1(Vdc)
5A3Dh
5A3Ch
Carrier speed setting,
2nd-motor
bb201
R/W
Same as bb101
0.1(kHz)
5A3Eh
5A3Dh
Sprinkle carrier pattern
selection, 2nd-motor
bb202
R/W
Same as bb102
-
5A3Fh
5A3Eh
Automatic-carrier reduction
selection, 2nd-motor
bb203
R/W
Same as bb103
-
5A78h
5A77h
Over current detection level,
2nd-motor
bb260
R/W
Same as bb160
0.1(A)
339Ah
3399h
Electronic thermal level set-
ting, 1st-motor
bC110
R/W
(0.0 - 3.0)
× Inverter rated current
*1
0.1(A)
339Bh
339Ah
Electronic thermal character-
istic selection, 1st-motor
bC111
R/W
00: Reduction characteristics
01: Constant torque characteris-
tics
02: Arbitrary setting
-
339Ch
339Bh
Electronic thermal Subtraction
function enable, 1st-motor
bC112
R/W
00: Disabled
01: Enabled
-
339Dh
339Ch
Electronic thermal Subtraction
time, 1st-motor
bC113
R/W
1 to 1000
1(s)
339Eh
339Dh
Electronic thermal counter
memory selection at
Power-off
bC-14
R/W
00: Disabled
01: Enabled
-
33A4h
33A3h
Free electronic thermal fre-
quency-1, 1st-motor
bC120
R/W
0.00 to [bC122] (Hz)
0.01(Hz)
33A5h
33A4h
Free electronic thermal cur-
rent-1, 1st-motor
bC121
R/W
(0.0 to 3.0)
× Inverter rated current
*1
0.1(A)
33A6h
33A5h
Free electronic thermal fre-
quency-2, 1st-motor
bC122
R/W
[bC120] to [bC124] (Hz)
0.01(Hz)
33A7h
33A6h
Free electronic thermal cur-
rent-2, 1st-motor
bC123
R/W
(0.0 to 3.0)
× Inverter rated current
*1
0.1(A)
33A8h
33A7h
Free electronic thermal fre-
quency-3, 1st-motor
bC124
R/W
[bC122] to 590.00 (Hz)
0.01(Hz)
33A9h
33A8h
Free electronic thermal cur-
rent-3, 1st-motor
bC125
R/W
(0.0 to 3.0)
× Inverter rated current
*1
0.1(A)
Register
No.
Modbus
register
spec. No.
Function name
Parame-
ter No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......