9 Communications Functions
9 - 72
High-function General-purpose Inverter RX2 Series User’s Manual
Precautions for Correct Use
Precautions for Correct Use
• The “Register No.” in the table header shows the register number used inside the inverter.
• The “Modbus register spec. No.” in the table header shows the register number used to actu-
ally specify the register in the Modbus communication process.
This register number is 1 less than the inverter “Register No.” according to the Modbus com-
munication specifications.
9-5-6
Group C Register List
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
36B1h
36B0h
Input terminal [1] function
CA-01
R/W
-
36B2h
36B1h
Input terminal [2] function
CA-02
R/W
36B3h
36B2h
Input terminal [3] function
CA-03
R/W
36B4h
36B3h
Input terminal [4] function
CA-04
R/W
36B5h
36B4h
Input terminal [5] function
CA-05
R/W
36B6h
36B5h
Input terminal [6] function
CA-06
R/W
36B7h
36B6h
Input terminal [7] function
CA-07
R/W
36B8h
36B7h
Input terminal [8] function
CA-08
R/W
36B9h
36B8h
Input terminal [9] function
CA-09
R/W
36Bah
36B9h
Input terminal [A] function
CA-10
R/W
36BBh
36BAh
Input terminal [B] function
CA-11
R/W
36C5h
36C4h
Input terminal [1] active state
CA-21
R/W
00: Normally open: NO
01: Normally closed: NC
-
36C6h
36C5h
Input terminal [2] active state
CA-22
R/W
36C7h
36C6h
Input terminal [3] active state
CA-23
R/W
36C8h
36C7h
Input terminal [4] active state
CA-24
R/W
36C9h
36C8h
Input terminal [5] active state
CA-25
R/W
36Cah
36C9h
Input terminal [6] active state
CA-26
R/W
36CBh
36CAh
Input terminal [7] active state
CA-27
R/W
36CCh
36CBh
Input terminal [8] active state
CA-28
R/W
36CDh
36CCh
Input terminal [9] active state
CA-29
R/W
36Ceh
36CDh
Input terminal [A] active state
CA-30
R/W
36CFh
36CEh
Input terminal [B] active state
CA-31
R/W
36D9h
36D8h
Input terminal [1] response time
CA-41
R/W
0 to 400
1(ms)
36Dah
36D9h
Input terminal [2] response time
CA-42
R/W
1(ms)
36DBh
36Dah
Input terminal [3] response time
CA-43
R/W
1(ms)
36DCh
36DBh
Input terminal [4] response time
CA-44
R/W
1(ms)
36DDh
36DCh
Input terminal [5] response time
CA-45
R/W
1(ms)
36Deh
36DDh
Input terminal [6] response time
CA-46
R/W
1(ms)
36DFh
36DEh
Input terminal [7] response time
CA-47
R/W
1(ms)
36E0h
36DFh
Input terminal [8] response time
CA-48
R/W
1(ms)
36E1h
36E0h
Input terminal [9] response time
CA-49
R/W
1(ms)
36E2h
36E1h
Input terminal [A] response time CA-50
R/W
1(ms)
36E3h
36E2h
Input terminal [B] response time CA-51
R/W
1(ms)
36E7h
36E6h
Multistage input determination
time
CA-55
R/W
0 to 2000
1(ms)
36Ech
36EBh
FUP/FDN overwrite target
selection
CA-60
R/W
00: Frequency command
01: PID1
-
36Edh
36ECh
FUP/FDN data save enable
CA-61
R/W
00: Not save
01: Save
-
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......