9 Communications Functions
9 - 76
High-function General-purpose Inverter RX2 Series User’s Manual
3798h
3797h
Output relay [AL] on-delay
time
CC-32
R/W
0 to 10000
0.01(s)
3799h
3798h
Output relay [AL] off-delay
time
CC-33
R/W
0 to 10000
0.01(s)
37A0h
379Fh
Logical calculation target 1
selection of LOG1
CC-40
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37A1h
37A0h
Logical calculation target 2
selection of LOG1
CC-41
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37A2h
37A1h
Logical calculation symbol
selection of LOG1
CC-42
R/W
00:AND
01:OR
02:XOR
-
37A3h
37A2h
Logical calculation target 1
selection of LOG2
CC-43
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37A4h
37A3h
Logical calculation target 2
selection of LOG2
CC-44
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37A5h
37A4h
Logical calculation symbol
selection of LOG2
CC-45
R/W
00:AND
01:OR
02:XOR
-
37A6h
37A5h
Logical calculation target 1
selection of LOG3
CC-46
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37A7h
37A6h
Logical calculation target 2
selection of LOG3
CC-47
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37A8h
37A7h
Logical calculation symbol
selection of LOG3
CC-48
R/W
00:AND
01:OR
02:XOR
-
37A9h
37A8h
Logical calculation target 1
selection of LOG4
CC-49
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37Aah
37A9h
Logical calculation target 2
selection of LOG4
CC-50
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37Abh
37AAh
Logical calculation symbol
selection of LOG4
CC-51
R/W
00:AND
01:OR
02:XOR
-
37Ach
37ABh
Logical calculation target 1
selection of LOG5
CC-52
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37Adh
37ACh
Logical calculation target 2
selection of LOG5
CC-53
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37Aeh
37ADh
Logical calculation symbol
selection of LOG5
CC-54
R/W
00:AND
01:OR
02:XOR
-
37Afh
37AEh
Logical calculation target 1
selection of LOG6
CC-55
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......