9 - 77
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-
5 Mod
bu
s Com
m
u
n
icat
ion
Regi
ster Nu
m
b
er
List
9
9-5-
6 Group C
Register
List
37B0h
37AFh
Logical calculation target 2
selection of LOG6
CC-56
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37B1h
37B0h
Logical calculation symbol
selection of LOG6
CC-57
R/W
00:AND
01:OR
02:XOR
-
37B2h
37B1h
Logical calculation target 1
selection of LOG7
CC-58
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37B3h
37B2h
Logical calculation target 2
selection of LOG7
CC-59
R/W
See <List of output terminal func-
tions> 062: LOG1 to 068: LOG7
cannot be selected.
-
37B4h
37B3h
Logical calculation symbol
selection of LOG7
CC-60
R/W
00:AND
01:OR
02:XOR
-
37DDh
37DCh
[FM] monitor output wave
form selection
Cd-01
R/W
00: PWM
01: frequency
-
37Deh
37DDh
[FM] monitor output base fre-
quency (at PWM output)
Cd-02
R/W
0 to 3600
1(Hz)
37DFh
37DEh
[FM] monitor output selection
Cd-03
R/W
See the List of output monitor
functions
*1
1
37E0h
37DFh
[Ao1] monitor output selection Cd-04
R/W
See the List of output monitor
functions
*1
1
37E1h
37E0h
[Ao2] monitor output selection Cd-05
R/W
See the List of output monitor
functions
*1
1
37E6h
37E5h
Analog monitor adjust mode
enable
Cd-10
R/W
00: Disabled
01: Enabled
-
37E7h
37E6h
Filter time constant of
[FM]monitor
Cd-11
R/W
1 to 500
1(ms)
37E8h
37E7h
[FM] Data type selection
Cd-12
R/W
00: absolute value
01: with sign
-
37E9h
37E8h
[FM] monitor bias adjustment
Cd-13
R/W
-1000 to 1000
0.1(%)
37Eah
37E9h
[FM] monitor gain adjustment
Cd-14
R/W
-10000 to 10000
0.1(%)
37Ebh
37EAh
Output level setting at [FM]
monitor adjust mode
Cd-15
R/W
-1000 to 1000
0.1(%)
37F1h
37F0h
Filter time constant of [Ao1]
monitor
Cd-21
R/W
1 to 500
1(ms)
37F2h
37F1h
[Ao1] Data type selection
Cd-22
R/W
00: absolute value
01: with sign
-
37F3h
37F2h
[Ao1] monitor bias adjustment Cd-23
R/W
-1000 to 1000
0.1(%)
37F4h
37F3h
[Ao1] monitor gain adjustment Cd-24
R/W
-10000 to 10000
0.1(%)
37F5h
37F4h
Output level setting at [Ao1]
monitor adjust mode
Cd-25
R/W
-1000 to 1000
0.1(%)
37FBh
37FAh
Filter time constant of [Ao2]
monitor
Cd-31
R/W
1 to 500
1(ms)
37FCh
37FBh
[Ao2] Data type selection
Cd-32
R/W
00: absolute value
01: with sign
-
37FDh
37FCh
[Ao2] monitor bias adjustment Cd-33
R/W
-1000 to 1000
0.1(%)
37Feh
37FDh
[Ao2] monitor gain adjustment Cd-34
R/W
-10000 to 10000
0.1(%)
37FFh
37FEh
Output level setting at [Ao2]
monitor adjust mode
Cd-35
R/W
-1000 to 1000
0.1(%)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......