9 Communications Functions
9 - 78
High-function General-purpose Inverter RX2 Series User’s Manual
3841h
3840h
Low current signal output
mode selection, 1st motor
CE101
R/W
00: During acceleration/decelera-
tion, at constant speed
01: Only at constant speed
-
3842h
3841h
Low current detection level 1,
1st motor
CE102
R/W
(0.0 to 2.0)
× Inverter rated current
*2
0.1(A)
3843h
3842h
Low current detection level 2,
1st motor
CE103
R/W
(0.0 to 2.0)
× Inverter rated current
*2
0.1(A)
3845h
3844h
Over current signal output
mode selection, 1st motor
CE105
R/W
00: During acceleration/decelera-
tion, at constant speed
01: Only at constant speed
-
3846h
3845h
Over current detection level 1,
1st motor
CE106
R/W
(0.0 to 2.0)
× Inverter rated current
*2
0.1(A)
3847h
3846h
Over current detection level 2,
1st motor
CE107
R/W
(0.0 to 2.0)
× Inverter rated current
*2
0.1(A)
384Ah
3849h
Arrival frequency setting
during acceleration 1
CE-10
R/W
0 to 59000
0.01(Hz)
384Bh
384Ah
Arrival frequency setting
during deceleration 1
CE-11
R/W
0 to 59000
0.01(Hz)
384Ch
384Bh
Arrival frequency setting
during acceleration 2
CE-12
R/W
0 to 59000
0.01(Hz)
384Dh
384Ch
Arrival frequency setting
during deceleration 2
CE-13
R/W
0 to 59000
0.01(Hz)
3854h
3853h
Over torque level (Forward
driving), 1st motor
CE120
R/W
0 to 5000
0.1(%)
3855h
3854h
Over torque level (Reverse
regenerative), 1st motor
CE121
R/W
0 to 5000
0.1(%)
3856h
3855h
Over torque level (Reverse
driving), 1st motor
CE122
R/W
0 to 5000
0.1(%)
3857h
3856h
Over torque level (Forward
regenerative), 1st motor
CE123
R/W
0 to 5000
0.1(%)
385Eh
385Dh
Electronic thermal warning
level (MTR)
CE-30
R/W
0 to 10000
0.01(%)
385Fh
385Eh
Electronic thermal warning
level (CTL)
CE-31
R/W
0 to 10000
0.01(%)
3861h
3860h
Zero speed detection level
CE-33
R/W
0 to 10000
0.01(Hz)
3862h
3861h
Cooling FAN over-heat warn-
ing level
CE-34
R/W
0 to 200
1(°C)
3864h
3863h
Accum.RUN
(RNT)/Accum.Power-on
(ONT) time setting
CE-36
(HIGH)
R/W
0 to 100000
1(hr)
3865h
3864h
CE-37
(LOW)
R/W
3868h
3867h
Window comparator for [Ai1]
higher level
CE-40
R/W
0 to 100
1(%)
3869h
3868h
Window comparator for [Ai1]
lower level
CE-41
R/W
0 to 100
1(%)
386Ah
3869h
Window comparator for [Ai1]
hysteresis width
CE-42
R/W
0 to 10
1(%)
386Bh
386Ah
Window comparator for [Ai2]
higher level
CE-43
R/W
0 to 100
1(%)
386Ch
386Bh
Window comparator for [Ai2]
lower level
CE-44
R/W
0 to 100
1(%)
386Dh
386Ch
Window comparator for [Ai2]
hysteresis width
CE-45
R/W
0 to 10
1(%)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......