9 Communications Functions
9 - 80
High-function General-purpose Inverter RX2 Series User’s Manual
38Bah
38B9h
EzCOM Start method
selection
CF-22
R/W
00: ECOM terminal
01: (Modbus spec)
-
38BBh
38BAh
EzCOM data size
CF-23
R/W
01 to 05
1
38BCh
38BBh
EzCOM destination address 1 CF-24
R/W
1 to 47
1
38BDh
38BCh
EzCOM destination resister 1
CF-25
R/W
0000 to FFFF
1
38Beh
38BDh
EzCOM source resister 1
CF-26
R/W
0000 to FFFF
1
38BFh
38BEh
EzCOM destination address 2 CF-27
R/W
1 to 247
1
38C0h
38BFh
EzCOM destination resister 2
CF-28
R/W
0000 to FFFF
1
38C1h
38C0h
EzCOM source resister 2
CF-29
R/W
0000 to FFFF
1
38C2h
38C1h
EzCOM destination address 3 CF-30
R/W
1 to 247
1
38C3h
38C2h
EzCOM destination resister 3
CF-31
R/W
0000 to FFFF
1
38C4h
38C3h
EzCOM source resister 3
CF-32
R/W
0000 to FFFF
1
38C5h
38C4h
EzCOM destination address 4 CF-33
R/W
1 to 247
1
38C6h
38C5h
EzCOM destination resister 4
CF-34
R/W
0000 to FFFF
1
38C7h
38C6h
EzCOM source resister 4
CF-35
R/W
0000 to FFFF
1
38C8h
38C7h
EzCOM destination address 5 CF-36
R/W
1 to 247
1
38C9h
38C8h
EzCOM destination resister 5
CF-37
R/W
0000 to FFFF
1
38Cah
38C9h
EzCOM source resister 5
CF-38
R/W
0000 to FFFF
1
38D6h
38D5h
USB communication Node
allocation
CF-50
R/W
1 to 247
1
5F51h
5F50h
Low current signal output
mode selection, 2nd-motor
CE201
R/W
Same as CE101
-
5F52h
5F51h
Low current detection level 1,
2nd-motor
CE202
R/W
Same as CE102
0.1(A)
5F53h
5F52h
Low current detection level 2,
2nd-motor
CE203
R/W
Same as CE103
0.1(A)
5F55h
5F54h
Over current signal output
mode selection, 2nd-motor
CE205
R/W
Same as CE105
-
5F56h
5F55h
Over current detection level 1,
2nd-motor
CE206
R/W
Same as CE106
0.1(A)
5F57h
5F56h
Over current detection level 2,
2nd-motor
CE207
R/W
Same as CE107
0.1(A)
5F64h
5F63h
Over torque level (Forward
driving), 2nd-motor
CE220
R/W
Same as CE120
0.1(%)
5F65h
5F64h
Over torque level (Reverse
regenerative), 2nd-motor
CE221
R/W
Same as CE121
0.1(%)
5F66h
5F65h
Over torque level (Reverse
driving), 2nd-motor
CE222
R/W
Same as CE122
0.1(%)
5F67h
5F66h
Over torque level (Forward
regenerative), 2nd motor
CE223
R/W
Same as CE123
0.1(%)
*1. 0 to 65535 (Register No. of d, F code)
*2. On the parameter about the current and the voltage, the figures and the units to be handled vary in the setting path.
1) Operator or CX-Drive: 0.1 A or 0.1 V (When CX-Drive is operated, set [CF-11] Resister data selection to 00 (A, V).
When the data of [CF-11] Resister data selection is not set to 00 (A, V), it is not set or displayed correctly.)
2) Modbus: The current and the voltage vary, depending on the setting of Resister data selection [CF-11].
When [CF-11] Resister data selection is set to 00 (A, V), 0.1 A, 0.1 V
When [CF-11] Resister data selection is set to 01 (%), 0.01% (Rated ratio)
3) Drive programming: 0.01% (Rated ratio)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......