9 - 83
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-
5 Mod
bu
s Com
m
u
n
icat
ion
Regi
ster Nu
m
b
er
List
9
9-5-
7 Group H
Register
List
3B2Fh
3B2Eh
Free-V/f Voltage 1 setting,
1st-motor
Hb151
R/W
0 to 10000
0.1(V)
3B30h
3B2Fh
Free-V/f frequency 2 setting,
1st-motor
Hb152
R/W
0 to 59000(Hb150) to (Hb154)
0.01(Hz)
3B31h
3B30h
Free-V/f Voltage 2 setting,
1st-motor
Hb153
R/W
0 to 10000
0.1(V)
3B32h
3B31h
Free-V/f frequency 3 setting,
1st-motor
Hb154
R/W
0 to 59000(Hb152) to (Hb156)
0.01(Hz)
3B33h
3B32h
Free-V/f Voltage 3 setting,
1st-motor
Hb155
R/W
0 to 10000
0.1(V)
3B34h
3B33h
Free-V/f frequency 4 setting,
1st-motor
Hb156
R/W
0 to 59000(Hb154) to (Hb158)
0.01(Hz)
3B35h
3B34h
Free-V/f Voltage 4 setting,
1st-motor
Hb157
R/W
0 to 10000
0.1(V)
3B36h
3B35h
Free-V/f frequency 5 setting,
1st-motor
Hb158
R/W
0 to 59000(Hb156) to (Hb160)
0.01(Hz)
3B37h
3B36h
Free-V/f Voltage 5 setting,
1st-motor
Hb159
R/W
0 to 10000
0.1(V)
3B38h
3B37h
Free-V/f frequency 6 setting,
1st-motor
Hb160
R/W
0 to 59000(Hb158) to (Hb162)
0.01(Hz)
3B39h
3B38h
Free-V/f Voltage 6 setting,
1st-motor
Hb161
R/W
0 to 10000
0.1(V)
3B3Ah
3B39h
Free-V/f frequency 7 setting,
1st-motor
Hb162
R/W
0 to 59000(Hb160) to (Hb104)
0.01(Hz)
3B3Bh
3B3Ah
Free-V/f Voltage 7 setting,
1st-motor
Hb163
R/W
0 to 10000
0.1(V)
3B42h
3B41h
Slip Compensation P-gain
witn encoder, 1st-motor
Hb170
R/W
0 to 1000
1(%)
3B43h
3B42h
Slip Compensation I-gain witn
encoder, 1st-motor
Hb171
R/W
0 to 1000
1(%)
3B4Ch
3B4Bh
Output voltage gain,
1st-motor
Hb180
R/W
0 to 255
1(%)
3B61h
3B60h
Automatic torque boost volt-
age compensation gain,
1st-motor
HC101
R/W
0 to 255
1(%)
3B62h
3B61h
Automatic torque boost slip
compensation gain, 1st-motor
HC102
R/W
0 to 255
1(%)
3B6Ah
3B69h
Zero speed area limit for
Async.M-0SLV, 1st-motor
HC110
R/W
0 to 100
1(%)
3B6Bh
3B6Ah
Boost value at start for
Async.M-SLV/IM-CLV,
1st-motor
HC111
R/W
0 to 50
1(%)
3B6Ch
3B6Bh
Boost value at start for
Async.M-0SLV, 1st-motor
HC112
R/W
0 to 50
1(%)
3B6Dh
3B6Ch
Secondary resistance correc-
tion, 1st-motor
HC113
R/W
00: Disabled
01: Enabled
-
3B6Eh
3B6Dh
Counter direction run protec-
tion selection, 1st-motor
HC114
R/W
00: Disabled
01: Enabled
-
3B74h
3B73h
Torque current reference filter
time constant, 1st-motor
HC120
R/W
0 to 100
1(ms)
3B75h
3B74h
Speed feedforward compen-
sation gain, 1st-motor
HC121
R/W
0 to 1000
1(%)
3BC6h
3BC5h
Sync. Motor capacity setting,
1st-motor
Hd102
R/W
1 to 16000
0.01(kW)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......