9 - 89
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-
5 Mod
bu
s Com
m
u
n
icat
ion
Regi
ster Nu
m
b
er
List
9
9-5-
8 Group P
Register List
Precautions for Correct Use
Precautions for Correct Use
• The “Register No.” in the table header shows the register number used inside the inverter.
• The “Modbus register spec. No.” in the table header shows the register number used to actu-
ally specify the register in the Modbus communication process.
This register number is 1 less than the inverter “Register No.” according to the Modbus com-
munication specifications.
9-5-8
Group P Register List
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
4269h
4268h
Mode selection for Emer-
gency-force drive
PA-01
R/W
00: Disabled
01: Enabled
-
426Ah
4269h
Frequency reference setting
at Emergency-force drive
PA-02
R/W
0 to 59000
0.01(Hz)
426Bh
426Ah
Direction command at Emer-
gency-force drive
PA-03
R/W
00: Normal rotation
01: Reverse rotation
-
426Ch
426Bh
Commercial power supply
bypass function selection
PA-04
R/W
00: Disabled
01: Enabled
-
426Dh
426Ch
Delay time of Bypass function PA-05
R/W
0 to 10000
0.1(s)
427Ch
427Bh
Simulation mode enable
PA-20
R/W
00: Disabled
01: Enabled
-
427Dh
427Ch
Error code selection for Alarm
test
PA-21
R/W
0 to 255
1
427Eh
427Dh
Output current monitor
optional output enable
PA-22
R/W
00: Disabled
01: Enabled: parameter setting
[PA-23]
02: Enabled: set from [Ai1]
03: Enabled: set from [Ai2]
04: Enabled: set from [Ai3]
05: (Reserved)
06: (Reserved)
07: (Reserved)
-
427Fh
427Eh
Output current monitor
optional output value setting
PA-23
R/W
0.0 to 3.0
× Inverter rated current
*1
0.1(A)
4280h
427Fh
DC-bus voltage monitor
optional output enable
PA-24
R/W
00: Disabled
01: Enabled: parameter setting
[PA-25]
02: Enabled: set from [Ai1]
03: Enabled: set from [Ai2]
04: Enabled: set from [Ai3]
05: (Reserved)
06: (Reserved)
07: (Reserved)
-
4281h
4280h
DC-bus voltage monitor
optional value output
PA-25
R/W
200V class: 0 to 4500
400V class: 0 to 9000
0.1(Vdc)
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......