9 - 95
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-
5 Mod
bu
s Com
m
u
n
icat
ion
Regi
ster Nu
m
b
er
List
9
9-5-
10 Group
o Register
List
Precautions for Correct Use
Precautions for Correct Use
• The “Register No.” in the table header shows the register number used inside the inverter.
• The “Modbus register spec. No.” in the table header shows the register number used to actu-
ally specify the register in the Modbus communication process.
This register number is 1 less than the inverter “Register No.” according to the Modbus com-
munication specifications.
4858h
4857h
EzSQ user parameter UL (09)
UF-20
(HIGH)
R/W
-2147483647 to 2147483647
1
4859h
4858h
UF-21
(LOW)
R/W
485Ah
4859h
EzSQ user parameter UL (10)
UF-22
(HIGH)
R/W
-2147483647 to 2147483647
1
485Bh
485Ah
UF-23
(LOW)
R/W
485Ch
485Bh
EzSQ user parameter UL (11)
UF-24
(HIGH)
R/W
-2147483647 to 2147483647
1
485Dh
485Ch
UF-25
(LOW)
R/W
485Eh
485Dh
EzSQ user parameter UL (12)
UF-26
(HIGH)
R/W
-2147483647 to 2147483647
1
485Fh
485Eh
UF-27
(LOW)
R/W
4860h
485Fh
EzSQ user parameter UL (13)
UF-28
(HIGH)
R/W
-2147483647 to 2147483647
1
4861h
4860h
UF-29
(LOW)
R/W
4862h
4861h
EzSQ user parameter UL (14)
UF-30
(HIGH)
R/W
-2147483647 to 2147483647
1
4863h
4862h
UF-31
(LOW)
R/W
4864h
4863h
EzSQ user parameter UL (15)
UF-32
(HIGH)
R/W
-2147483647 to 2147483647
1
4865h
4864h
UF-33
(LOW)
R/W
9-5-10 Group o Register List
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
3E8Ah
3E89h
Operation mode on option
card error (SLOT-1)
oA-10
R/W
00: Error
01: Continue operation
-
3E8Bh
3E8Ah
Communication Watch Dog
Timer
oA-11
R/W
0 to 10000
0.01(s)
3E8Ch
3E8Bh
Action selection at communi-
cation error
oA-12
R/W
00: Error
01: Trip after deceleration stop
02: Ignore
03: Free run
04: Deceleration stop
-
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......