9 Communications Functions
9 - 98
High-function General-purpose Inverter RX2 Series User’s Manual
*2. The management inverter sends the master switching command from Inverter No. 01 to 02 after data is sent
from Inverter 01 (master) to a slave (or slaves), with a wait time of “silent interval
Communication Wait Time.
*3. After receiving data from the master inverter, the management inverter sends the next master switching com-
mand with a wait time of “silent interval
Communication Wait Time. If the management inverter cannnot
receive the data sent from the master inverter within the Communication Error Timeout Time, a communica-
tion timeout occurs and the management inverter follows the operation set in the Operation Selection on
Communication Error.
*4. Be sure to enable the Communication Error Timeout Time setting (= 0.01 to 99.99) on the management
inverter. When this setting is disabled (= 0), the co-inverter communication will stop if the management
inverter cannot receive data from the master. In this case, cycle the power supply for the management
inverter, or reset the management inverter (by turning ON/OFF the terminal RS).
The parameters required to establish Inter-inverter communication are shown in the table below.
9-6-1
Inter-inverter Communication Parameters
Parameter No.
Function name
Data
Default
data
Unit
Setting
target
*1
CF-02
*2
Communication
Station No. Selection
1 to 247
*3
1
ALL
*4
CF-05
*5
Operation Selection on
Communication Error
00:
Trip
02
ALL
01:
Trip after deceleration stop
02:
Ignore
03:
Free-run stop
04:
Deceleration stop
CF-06
Communication Error
Timeout Time
0.00:
Timeout disabled
0.00
s
ALL
0.01 to 99.99
CF-07
Communication Wait
Time
0 to 1000
0
ms
ALL
CF-08
*2
Communication Selec-
tion
00:
Modbus communication
00
01:
EzCom communication
B
02:
EzCom communication
(management inverter)
A
CF-20
*2
EzCom Communica-
tion Starting Station
Number
1 to 8
Setting required only for manage-
ment inverter
*6
1
A
CF-21
*2
EzCom Communica-
tion Ending Station
Number
1 to 8
Setting required only for manage-
ment inverter
*6
1
A
CF-22
*2
EzCom Communica-
tion Start Selection
00:
Start via input terminal
*7
00
A
01:
Constant communication
*8
A
CF-23
Number of Sent Data
of All Stations in
EzCom Communica-
tion
1 to 5
5
M
CF-24
Recipient Station
Number of All Stations
in EzCom Communi-
cation 1
1 to 247
*9
1
M
CF-25
Recipient Register of
All Stations in EzCom
Communication 1
0000 to FFFF
0
M
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......