12 - 21
12 Troubleshooting
High-function General-purpose Inverter RX2 Series User’s Manual
12-2 Error No
. and
Its Meas
ure
12
12-
2-2
D
etails about Er
rors
When the current position counter exceeds the position control ranges for normal/reverse rotation in the
setting of [AE-52] position range (normal) or [AE-54] position range (reverse), the inverter turns OFF its
output and displays the error.
Related pages found herein: P. 8-110
When the deviation between the frequency command and the feedback speed exceeds the [bb-83]
speed deviation error detection level setting, the inverter judges it as an error. If “01: Error” is specified
for [bb-82] Operation for speed deviation error, the inverter turns ON the output terminal function 041
[DSE] with a speed deviation error, turns OFF the inverter output, and displays this error.
Related pages found herein: P. 8-78
When the [bb-87] abnormal position deviation time passes with the deviation of the position feedback
against the position command exceeding the [bb-86] abnormal position deviation detection level, it is
determined to be abnormal. When the behavior of the abnormal position deviation [bb-85] has been set
to 01, the output terminal [PDD] is turned ON, the output is turned OFF, and the error is displayed.
Related pages found herein: P. 8-100
E104 Position Control Range Error
Occurrence
Estimated cause(s)
Exemplar measures to be taken
Error occurred
during operation.
Recheck the setting of
electronic gear.
Re-examination of operation condition or correction of load
condition may improve the situation.
A slip occurs due to
improper encoder set-
ting.
Check the encoder mounting state. If any, re-examine factors
for slipping.
Improper encoder setting Check the setting of encoder constant and the like.
Improper electronic gear
setting
Recheck the setting of electronic gear.
E105 Speed Deviation Error
Occurrence
Estimated cause(s)
Exemplar measures to be taken
Error occurred
during operation.
Recheck the setting of
electronic gear.
Re-examination of operation condition or correction of load
condition may improve the situation.
A slip occurs due to
improper encoder set-
ting.
Check the encoder mounting state. If any, re-examine factors
for slipping.
Improper encoder setting Check the setting of encoder constant and the like.
Improper electronic gear
setting
Recheck the setting of electronic gear.
E106 Position Deviation Error
Occurrence
Estimated cause(s)
Exemplar measures to be taken
Error occurred
during operation.
Recheck the setting of
electronic gear.
Re-examination of operation condition or correction of load
condition may improve the situation.
A slip occurs due to
improper encoder set-
ting.
Check the encoder mounting state. If any, re-examine factors
for slipping.
Improper encoder setting Check the setting of encoder constant and the like.
Improper electronic gear
setting
Recheck the setting of electronic gear.
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......