12 - 29
12 Troubleshooting
High-function General-purpose Inverter RX2 Series User’s Manual
12-3
Alarm D
isplay
and
Its Measu
res
12
12-
3-2
C
hecking Inconsistent Settings
You need to take a measure according to the warning number and the type of warning. Refer to the
table below.
The induction motor (IM) control and synchronous motor (permanent magnetic motor) (SM (PMM)) con-
trol can be switched in [AA121].
12-3-2 Checking Inconsistent Settings
Occurrence
Estimated cause(s)
Exemplar measures to be taken
Warning was
generated -
102
(First Max. frequency) < (first upper limiter)
IM: [Hb105] < [bA102]
SM (PMM): [Hd105] < [bA102]
• Increase the Max. frequency
[Hb105]/[Hd105].
• Decrease the upper limiter [bA102].
Warning was
generated -
103
(First Max. frequency) < (first lower limiter)
IM: [Hb105] < [bA103]
SM (PMM): [Hd105] < [bA103]
• Increase the Max. frequency
[Hb105]/[Hd105].
• Decrease the lower limiter [bA103].
Warning was
generated -
106
(First Max. frequency) < (first main speed command)
IM: [Hb105] < [Ab110]
SM (PMM): [Hd105] < [Ab110]
• Increase the Max. frequency
[Hb105]/[Hd105].
• Decrease the main speed command
[Ab110].
Warning was
generated -
107
(First Max. frequency) <
(first auxiliary speed command)
IM: [Hb105] < [AA104]
SM (PMM): [Hd105] < [AA104]
• Increase the Max. frequency
[Hb105]/[Hd105].
• Decrease the auxiliary speed com-
mand [AA104].
Warning was
generated -
202
(Second Max. frequency) < (second upper limiter)
IM: [Hb205] < [bA202]
SM (PMM): [Hd205] < [bA202]
• Increase the Max. frequency
[Hb205]/[Hd205].
• Decrease the upper limiter [bA202].
Warning was
generated -
203
(Second Max. frequency) < (second lower limiter)
IM: [Hb205] < [bA203]
SM (PMM): [Hd205] < [bA203]
• Increase the Max. frequency
[Hb105]/[Hd105].
• Decrease the lower limiter [bA103].
Warning was
generated -
206
(Second Max. frequency) <
(second main speed command)
IM: [Hb205] < [Ab210]
SM (PMM): [Hd205] < [Ab210]
• Increase the Max. frequency
[Hb205]/[Hd205].
• Decrease the main speed command
[Ab210].
Warning was
generated -
207
(Second Max. frequency) <
(second auxiliary speed command)
IM: [Hb205] < [AA204]
SM (PMM): [Hd205] < [AA204]
• Increase the Max. frequency
[Hb205]/[Hd205].
• Decrease the auxiliary speed com-
mand [AA204].
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......