13 Maintenance and Inspection
13 - 4
High-function General-purpose Inverter RX2 Series User’s Manual
13-3 Inspection Items
Target
section
Item
Details
Interval
Method
Criteria
Mea-
sure-
ment
instru-
ment
Daily
Periodic
1
year
2
years
General
Ambient
environment
Check the ambi-
ent temperature,
humidity, dust,
etc.
○
See the installation
method.
The ambient tem-
perature and humidity
are within the usable
range. No freezing,
condensation, dust,
corrosive gas, explo-
sive gas, flammable
gas, mist of grinding
fluid, hydrogen sul-
fide, and salts are
permissible
Ther-
mometer
Hydrom-
eter
Recorder
Entire device
No abnormal
vibration or
sound is
observed.
○
By visual check and
hearing
There must be no
abnormality.
Power supply
voltage
The main circuit
voltage is normal.
○
Measure line volt-
age between
inverter main circuit
terminals R, S, and
T.
They are within the
allowable variation
range of AC voltage.
Tester
and
digital
multime-
ter
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......