2 Design
2 - 26
High-function General-purpose Inverter RX2 Series User’s Manual
Precautions for Correct Use
• [AL] function is assigned to [CC-07] C contact relay of AL1-AL0/AL2-AL0 as initial state. Set
the alarm signal of output terminal 017 [AL] function to any of [CC-01] to [CC-07] and outputs
the signal.
The behavior of alarm relay AL1-AL0/AL2-AL0 is shown in the below table.
Precautions for Correct Use
• Factory default settings are shown below. You can change the setting for your needs.
Analog input terminal setting switch: Ai1 (SW1) = Voltage input, Ai2 (SW2) = Current input
Analog output terminal setting switch: Ao1 (SW3) = Voltage output, Ao2 (SW4) = Current
output
• When shipped from the factory, wiring is performed so that STO input is disabled.
• Do not short between the analog power supply H and L terminals, power supply P+ and P-
terminals, P24 and P- terminals, P+ and CM1 terminals, and P24 and CM1 terminals. Other-
wise, the inverter may fail.
[CC-17]
Control
power supply
Inverter error output
Output terminal states
AL1-AL0
AL2-AL0
00
ON
Normal
Open
Close
Alarm output
Close
Open
OFF
-
Open
Close
01
ON
Normal
Close
Open
Alarm output
Open
Close
OFF
-
Open
Close
Wiring Portion Above Control Circuit
P+
P24
P-
FM
RP
SN
SP
SN
SP
CM1
ED-
ED+
Ao2
Ao1
H
Ai1
Ai2
Ai3
L
L
TH-
TH+
P24S STC CMS
ST1
ST2
STC
Digital output
Modbus communication
EDM output
Control circuit terminal area
External 24V
terminal
Power supply
24V terminal
STO input
External thermistor
terminal
Analog input/output
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......