Appendices B STO Function
B - 12
High-function General-purpose Inverter RX2 Series User’s Manual
B-3 Example of Use
Procedure for connecting STO input to a safety controller is shown as an example.
The condition for use is the followings:
• Use external power supply as one for STO input.
• Never use EDM output.
Power supply connected to control terminals in 3G3RX2-series is needed to comply with SELV and
PELV.
Each ST1/ST2 signal must be separated physically and protected appropriately.
Device for communication of STO signals shall comply with safety standards like ISO13849-1 and
IEC61508, etc.
A safety system includes 3G3RX2-series must fulfill CAT.3, PL e /SIL3. Therefore, the 3G3RX2-series
must be combined with external safety devices that meet PL e/SIL3.
Test pulse input to ST1/ST2 shall be 300 us or less.
Combination of 3G3RX2-series with external safety devices is shown as below.
B-3-1
Example of Wiring
B-3-2
External Device
Manufacturer
Product Model
Applicable standard/criteria
OMRON
G9SA-301
ISO13849-1 cat4, SIL3
OMRON
G9SX-GS226-T15-RC
IEC61508 SIL1 to 3
OMRON
NE1A-SCPU01-V1
IEC61508 SIL3
OMRON
G9SP-N
IEC61508 SIL3
Separated physically or
provided cable protection
(double shielded)
STO Input
Reset
Switch
Safety switch
(Ex: Emergency Button)
STO Output
Safety unit
* Applicable standard
(IEC61508, ISO13849)
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......