C - 21
Appendices C Table of Parameters
High-function General-purpose Inverter RX2 Series User’s Manual
C-
3 Paramet
er List
C
C-3 Parameter List
Parameter Mode (Code A)
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
AA101
-
Main speed input source selec-
tion, 1st-motor
01 (Ai1 terminal input)/02 (Ai2 terminal input)/
03 (Ai3 terminal input)/04 (Reserved)/05 (Reserved)/
06 (Reserved)/07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)/
12 (Pulse string input: main unit)/
13 (Pulse string input: Option)/14 (Program function)/
15 (PID calculation)/16 (Reserved)
01
*1
AA102
-
Sub frequency input source
selection, 1st-motor
00 (Disabled)/01 (Ai1 terminal input)/02 (Ai2 terminal input)/
03 (Ai3 terminal input)/04 (Reserved)/05 (Reserved)/
06 (Reserved)/07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)/
12 (Pulse string input: main unit)/
13 (Pulse string input: Option)/14 (Program function)/
15 (PID calculation)/16 (Reserved)
00
AA104
○
Sub speed setting, 1st-motor
0.00 to 590.00 (Hz)
0.00
AA105
-
Calculation symbol selection for
Speed reference, 1st-motor
00 (Disabled)/01 (Addition)/02 (Subtraction)/
03 (Multiplication)
00
AA106
○
Add frequency setting,
1st-motor
-590.00 to 590.00 (Hz)
0.00
AA111
-
Run-command input source
selection, 1st-motor
00 ([FW]/[RV] terminal)/01 (3 wire)/
02 (RUN key on LCD operator)/03 (RS485)/
04 (Option 1)/05 (Option 2)/06 (Option 3)
00
*1
AA-12
○
RUN-key Direction of LCD oper-
ator, 1st-motor
00 (Normal rotation)/01 (Reverse rotation)
00
AA-13
-
STOP-key enable at RUN-com-
mand from terminal, 1st-motor
00 (Disabled)/01 (Enabled)/
02 (Only reset is enabled)
01
AA114
-
RUN-direction restriction,
1st-motor
00 (No limitation)/01 (Only normal rotation)/
02 (Only reverse rotation)
00
AA115
-
STOP mode selection,
1st-motor
00 (Deceleration stop)/01 (Free run stop)
00
AA121
-
Control mode selection,
1st-motor
00 ([V/f] Fixed torque characteristics (IM))/
01 ([V/f] Reducing torque characteristics (IM))/
02 ([V/f] Free V/f (IM))/03 ([V/f] Auto torque boost (IM))/
04 ([V/f with sensor] Fixed torque characteristics (IM)/
05 ([V/f with sensor] Reduced torque characteristics (IM)/
06 ([V/f with sensor] Free V/f (IM)/
07 ([V/f with sensor] Auto torque boost (IM)/
08 (Sensorless vector control (IM))/
09 (Zero-Hz range sensorless vector control (IM))
*2
/
10 (Vector control with sensor (IM))
*2
/
11 (Synchronous start type sensorless vector control
(SM/PMM))/
12 (IVMS start type sensorless vector control (SM/PMM))
*3
00
AA123
-
Vector control mode selection,
1st-motor
00 (Speed/torque control mode)/
01 (Pulse string position control mode)/
02 (Absolute position control mode)/
03 (High-resolution absolute position control mode)
00
AA201
-
Main speed input source selec-
tion, 2nd-motor
01 (Ai1 terminal input)/02 (Ai2 terminal input)/
03 (Ai3 terminal input)/04 (Reserved)/05 (Reserved)/
06 (Reserved)/07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)/
12 (Pulse string input: main unit)/
13 (Pulse string input: Option)/14 (Program function)/
15 (PID calculation)/16 (Reserved)
00
*1
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......