Appendices C Table of Parameters
C - 26
High-function General-purpose Inverter RX2 Series User’s Manual
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial value
Note
AE-01
-
Electronic gear setting point selec-
tion
00 (Feedback side)/01 (Command side)
00
AE-02
-
Electronic gear ratio numerator
1 to 10000
1
AE-03
-
Electronic gear ratio denominator
1 to 10000
1
AE-04
-
Positioning completion range set-
ting
0 to 1000 (ms)
5
AE-05
-
Positioning completion delay time
setting
0.00 to 10.00 (s)
0.00
AE-06
-
Position feed-forward gain setting
0.00 to 655.35
0.00
AE-07
-
Position loop gain setting
0.00 to 100.00
0.50
AE-08
-
Position bias setting
-2048 to 2048
0
AE-10
-
Stop position selection of Home
search function
00 (Parameter setting)/01 (Option 1)/
02 (Option 2)/03 (Option 3)
00
AE-11
○
Stop position of Home search
function
0 to 4095
0
AE-12
○
Speed reference of Home search
function
0.00 to 120.00
0.00
AE-13
-
Direction of Home search function
00 (Normal rotation)/01 (Reverse rotation)
00
AE-20
○
Position reference 0 setting
-268435455 to 268435455
In high resolution mode: -1073741823 to
1073741823
0
AE-22
○
Position reference 1 setting
0
AE-24
○
Position reference 2 setting
0
AE-26
○
Position reference 3 setting
0
AE-28
○
Position reference 4 setting
0
AE-30
○
Position reference 5 setting
0
AE-32
○
Position reference 6 setting
0
AE-34
○
Position reference 7 setting
0
AE-36
○
Position reference 8 setting
0
AE-38
○
Position reference 9 setting
0
AE-40
○
Position reference 10 setting
0
AE-42
○
Position reference 11 setting
0
AE-44
○
Position reference 12 setting
0
AE-46
○
Position reference 13 setting
0
AE-48
○
Position reference 14 setting
0
AE-50
○
Position reference 15 setting
0
AE-52
○
Position control range setting (for-
ward)
0 to 268435455
In high resolution mode: 0 to 1073741823
268435455
AE-54
○
Position control range setting
(reverse)
-268435455 to 0
In high resolution mode: -1073741823 to 0
-268435455
AE-56
-
Position control mode selection
00 (With limit)/01 (Without limit)
00
AE-60
○
Teach-in function target selection
00 (X00) to 15 (X15)
00
AE-61
-
Current position saving at
power-off
00 (Disabled)/01 (Enabled)
00
AE-62
○
Preset position data
-268435455 to 268435455
In high resolution mode: -1073741823 to
1073741823
0
AE-64
○
Deceleration stop distance calcu-
lation Gain
50.00 to 200.00
100.00
AE-65
○
Deceleration stop distance calcu-
lation Bias
0.00 to 655.35
0.00
AE-66
○
Speed Limit in APR control
0.00 to 100.00
1.00
AE-67
○
APR start speed
0.00 to 100.00
0.20
AE-70
-
Homing function selection
00 (Low speed zero return)/
01 (High speed zero return)/
02 (High speed zero return 2)
00
AE-71
-
Direction of homing function
00 (Normal rotation)/01 (Reverse rotation)
00
AE-72
○
Low-speed of homing function
0.00 to 10.00 (Hz)
0.00
AE-73
○
High-Speed of homing function
0.00 to 590.00 (Hz)
0.00
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......