C - 29
Appendices C Table of Parameters
High-function General-purpose Inverter RX2 Series User’s Manual
C-
3 Paramet
er List
C
AF244
○
Braking Frequency, 2nd-motor
(Reverse side)
0.00 to 590.00 (Hz)
0.00
AF250
○
Brake open delay time, 2nd-motor
0.00 to 2.00 (s)
0.20
AF251
○
Brake close delay time, 2nd-motor
0.00 to 2.00 (s)
0.20
AF252
○
Brake answer back check time,
2nd-motor
0.00 to 5.00 (s)
0.10
AF253
○
Servo lock/ DC injection time at
start, 2nd-motor
0.00 to 10.00 (s)
0.60
AF254
○
Servo lock/ DC injection time at
stop, 2nd-motor
0.00 to 10.00 (s)
0.60
*1. On the parameter about the current and the voltage, the figures and the units to be handled vary in the setting path.
1) Operator or CX-Drive: 0.1 A or 0.1 V (When CX-Drive is operated, set [CF-11] Resister data selection to 00 (A,V). When the data of
[CF-11] Resister data selection is not set to 00 (A,V), it is not set or displayed correctly.)
2) Modbus: The current and the voltage vary, depending on the setting of Resister data selection [CF-11].
When [CF-11] Resister data selection is set to 00 (A,V), 0.1 A, 0.1 V
When [CF-11] Resister data selection is set to 01 (%), 0.01% (Rated ratio)
3) Drive programming: 0.01% (Rated ratio)
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
AG101
○
Jump frequency 1, 1st-motor
0.00 to 590.00 (Hz)
0.00
AG102
○
Jump frequency width 1, 1st-motor 0.00 to 10.00 (Hz)
0.00
AG103
○
Jump frequency 2, 1st-motor
0.00 to 590.00 (Hz)
0.00
AG104
○
Jump frequency width 2, 1st-motor 0.00 to 10.00 (Hz)
0.00
AG105
○
Jump frequency 3, 1st-motor
0.00 to 590.00 (Hz)
0.00
AG106
○
Jump frequency width 3, 1st-motor 0.00 to 10.00 (Hz)
0.00
AG110
○
Acceleration stop frequency set-
ting, 1st-motor
0.00 to 590.00 (Hz)
0.00
AG111
○
Acceleration stop time setting,
1st-motor
0.0 to 60.0 (s)
0.0
AG112
○
Deceleration stop frequency set-
ting, 1st-motor
0.00 to 590.00 (Hz)
0.00
AG113
○
Deceleration stop time setting,
1st-motor
0.0 to 60.0 (s)
0.0
AG-20
○
Jogging frequency
0.00 to 10.00 (Hz)
6.00
AG-21
-
Jogging stop mode selection
00 (Disabled during FRS operation at stop)/
01 (Disabled during deceleration stop operation)/
02 (Disabled during DB operation at stop)/
03 (Enabled during FRS operation at stop)/
04 (Enabled during deceleration stop operation)/
05 (Enabled during DB operation at stop)
00
AG201
○
Jump frequency 1, 2nd-motor
0.00 to 590.00 (Hz)
0.00
AG202
○
Jump frequency width 1,
2nd-motor
0.00 to 10.00 (Hz)
0.00
AG203
○
Jump frequency 2, 2nd-motor
0.00 to 590.00 (Hz)
0.00
AG204
○
Jump frequency width 2,
2nd-motor
0.00 to 10.00 (Hz)
0.00
AG205
○
Jump frequency 3, 2nd-motor
0.00 to 590.00 (Hz)
0.00
AG206
○
Jump frequency width 3,
2nd-motor
0.00 to 10.00 (Hz)
0.00
AG210
○
Acceleration stop frequency set-
ting, 2nd-motor
0.00 to 590.00 (Hz)
0.00
AG211
○
Acceleration stop time setting,
2nd-motor
0.0 to 60.0 (s)
0.0
AG212
○
Deceleration stop frequency set-
ting, 2nd-motor
0.00 to 590.00 (Hz)
0.00
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial value
Note
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......