AH-42
-
Input source selection of Set-point
2 for PID1
00 (None)/01 (Ai1 terminal input)/02 (Ai2 terminal input)/
03 (Ai3 terminal input)/04 (Reserved)/05 (Reserved)/
06 (Reserved)/07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)/
12 (Pulse string input: main unit)/
13 (Pulse string input: Option)
00
AH-44
○
Set-point 2 setting for PID1
-100.00 to 100.00 (%)
*1
0.00
AH-46
-
Input source selection of Set-point
3 for PID1
00 (None)/01 (Ai1 terminal input)/02 (Ai2 terminal input)/
03 (Ai3 terminal input)/04 (Reserved)/05 (Reserved)/
06 (Reserved)/07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)/
12 (Pulse string input: main unit)/
13 (Pulse string input: Option)
00
AH-48
○
Set-point 3 setting for PID1
-100.00 to 100.00 (%)
*1
0.00
AH-50
-
Calculation symbol selection of
Set-point 1 for PID1
01 (Addition)/02 (Subtraction)/03 (Multiplication)/
04 (Division)/05(Minimum deviation)/
06(Maximum deviation)
01
AH-51
-
Input source selection of Process
data 1 for PID1
00 (None)/01 (Ai1 terminal input)/02 (Ai2 terminal input)/
03 (Ai3 terminal input)/04 (Reserved)/05 (Reserved)/
06 (Reserved)/08 (RS 485)/09 (Option 1)/10 (Option 2)/
11 (Option 3)/12 (Pulse string input: main unit)/
13 (Pulse string input: Option)
01
AH-52
-
Input source selection of Process
data 2 for PID1
00
AH-53
-
Input source selection of Process
data 3 for PID1
00
AH-54
-
Calculation symbol selection of
Process data for PID1
01 (Addition)/02 (Subtraction)/03 (Multiplication)/
04 (Division)/05(Square root of FB1)/
06(Square root of FB2)/07(Square root of (FB1-FB2))/
08(Average of PV-1 to PV-3)/
09(Minimum data of PV-1 to PV-3)/
10(Maximum data of PV-1 to PV-3)
01
AH-60
-
PID1 gain change method selec-
tion
00 (Only gain 1)/01 ([PRO] terminal switch)
00
AH-61
○
PID1 proportional gain 1
0.0 to 100.0
1.0
AH-62
○
PID1 integral time constant 1
0.0 to 3600.0 (s)
1.0
AH-63
○
PID1 derivative gain 1
0.00 to 100.00 (s)
0.00
AH-64
○
PID1 proportional gain 2
0.0 to 100.0
0.0
AH-65
○
PID1 integral time constant 2
0.00 to 3600.0 (s)
0.0
AH-66
○
PID1 derivative gain 2
0.00 to 100.00 (s)
0.00
AH-67
○
PID1 gain change time
0 to 10000 (ms)
100
AH-70
-
PID feed-forward selection
00 (Disabled)/01 (Ai1 terminal input)/
02 (Ai2 terminal input)/03 (Ai3 terminal input)/
04 (Reserved)/05 (Reserved)/06 (Reserved)
00
AH-71
○
PID1 output range
0.00 to 100.00 (%)
0.00
AH-72
○
PID1 deviation over level
0.00 to 100.00 (%)
3.00
AH-73
○
PID1 feedback compare signal
turn-off level
0.00 to 100.00 (%)
100.00
AH-74
○
PID1 feedback compare signal
turn-on level
0.00 to 100.00 (%)
0.00
AH-75
-
PID soft-start function enable
00 (Disabled)/01 (Enabled)
00
AH-76
○
PID soft-start target level
0.00 to 100.00 (%)
100.00
AH-78
○
Acceleration time setting for PID
soft-start function
0.00 to 3600.00 (s)
30.00
AH-80
○
PID soft-start time
0.00 to 100.00 (s)
0.00
AH-81
-
PID soft start error detection
enable
00 (Disabled)/01 (Enabled: error output)/
02 (Enabled: warning)
00
AH-82
○
PID soft start error detection level
0.00 to 100.00 (%)
0.00
AH-85
-
PID sleep trigger selection
00 (Disabled)/01 (Low output)/02 ([SLEP] terminal)
00
AH-86
○
PID sleep start level
0.00 to 590.00 (Hz)
0.00
AH-87
○
PID sleep active time
0.00 to 100.00 (s)
0.00
AH-88
-
Setpoint boost before PID sleep
enable
00 (Disabled)/01 (Enabled)
00
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......