Appendices C Table of Parameters
C - 32
High-function General-purpose Inverter RX2 Series User’s Manual
AH-89
○
Setpoint boost time
0.00 to 100.00 (s)
0.00
AH-90
○
Setpoint boost value
0.00 to 100.00 (%)
0.00
AH-91
○
Minimum RUN time befor PID
sleep
0.00 to 100.00 (s)
0.00
AH-92
○
Minimum active time of PID sleep
0.00 to 100.00 (s)
0.00
AH-93
-
PID sleep trigger selection
01 (Deviation amount)/02 (Low feedback)/
03 ([WAKE] terminal)
01
AH-94
○
PID wake start level
0.00 to 100.00 (%)
0.00
AH-95
○
PID wake start time
0.00 to 100.00 (s)
0.00
AH-96
○
PID wake start deviation value
0.00 to 100.00 (%)
0.00
*1. Data range differs depending on [AH-04] to [AH-06].
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
AJ-01
-
PID2 enable
00 (Disabled)/
01 (Enabled Without reverse output)/
02 (Enabled With reverse output)
00
AJ-02
-
PID2 deviation inverse
00 (Disabled)/01 (Enabled)
00
AJ-03
-
PID2 unit selection
on page C-70 at the end of Appendices
C
01
AJ-04
○
PID2 scale adjustment (0%)
-10000 to 10000
0
AJ-05
○
PID2 scale adjustment (100%)
-10000 to 10000
10000
AJ-06
○
PID2 scale adjustment (point
position)
0 to 4
2
AJ-07
-
Input source selection of
Set-point for PID2
00 (None)/01 (Ai1 terminal input)/02 (Ai2 terminal input)/
03 (Ai3 terminal input)/04 (Reserved)/05 (Reserved)/
06 (Reserved)/07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)/
12 (Pulse string input: main unit)/
13 (Pulse string input: Option)/15 (PID1 output)
07
AJ-10
○
Set-point setting for PID2
-100.00 to 100.00 (%)
*1
0.00
AJ-12
-
Input source selection of Pro-
cess data for PID2
00 (None)/01 (Ai1 terminal input)/02 (Ai2 terminal input)/
03 (Ai3 terminal input)/04 (Reserved)/05 (Reserved)/
06 (Reserved)/07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)/
12 (Pulse string input: main unit)/
13 (Pulse string input: Option)
02
AJ-13
○
PID2 proportional gain
0.0 to 100.0
1.0
AJ-14
○
PID2 integral time constant
0.0 to 3600.0 (s)
1.0
AJ-15
○
PID2 derivative gain
0.00 to 100.00 (s)
0.00
AJ-16
○
PID2 output range
0.00 to 100.00 (%)
0.00
AJ-17
○
PID2 deviation over level
0.00 to 100.00 (%)
3.00
AJ-18
○
PID2 feedback compare signal
turn-OFF level
0.00 to 100.00 (%)
100.00
AJ-19
○
PID2 feedback compare signal
turn-ON level
0.00 to 100.00 (%)
0.00
AJ-21
-
PID3 enable
00 (Disabled)/
01 (Enabled Without reverse output)/
02 (Enabled With reverse output)
00
AJ-22
-
PID3 deviation inverse
00 (Disabled)/01 (Enabled)
00
AJ-23
-
PID3 unit selection
on page C-70 at the end of Appendices
C
01
AJ-24
○
PID3 scale adjustment (0%)
-10000 to 10000
0
AJ-25
○
PID3 scale adjustment (100%)
-10000 to 10000
10000
AJ-26
○
PID3 scale adjustment (point
position)
0 to 4
2
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......