Appendices C Table of Parameters
C - 36
High-function General-purpose Inverter RX2 Series User’s Manual
bA201
-
Frequency limit selection, 2nd
motor
00 (Disabling)/01 (Ai1 terminal input)/
02 (Ai2 terminal input)/03 (Ai3 terminal input)/
04 (Reserved)/05 (Reserved)/06 (Reserved)/
07 (Parameter setting)/08 (RS485)/09 (Option 1)/
10 (Option 2)/11 (Option 3)/
12 (Pulse string input (main body))/
13 (Pulse string input Option)
00
bA202
○
Upper frequency limit, 2nd
motor
0.00 to 590.00 (Hz)
0.00
bA203
○
Lower frequency limit, 2nd
motor
0.00 to 590.00 (Hz)
0.00
bA210
-
Torque limit selection,
2nd-motor
00 (Disable)/01 (Ai1 terminal input)/
02 (Ai2 terminal input)/03 (Ai3 terminal input)/
04 (Reserved)/05 (Reserved)/06 (Reserved)/
07 (Parameter setting)/08 (RS 485)/
09 (Option 1)/10 (Option 2)/11 (Option 3)
07
bA211
-
Torque limit parameter mode
selection, 2nd-motor
00 (Four quadrant specific)/
01 ([TRQ] terminal switch)
00
bA212
○
Torque limit 1 (Forward driving),
2nd-motor
0.0 to 500.0 (%)
(Limited at at torque equivalent to 200% of
inverter ND rating)
150.0 (%)
bA213
○
Torque limit 2 (Reverse regener-
ative), 2nd-motor
0.0 to 500.0 (%)
(Limited at at torque equivalent to 200% of
inverter ND rating)
150.0 (%)
bA214
○
Torque limit 3 (Reverse driv-
ing), 2nd-motor
0.0 to 500.0 (%)
(Limited at at torque equivalent to 200% of
inverter ND rating)
150.0 (%)
bA215
○
Torque limit 4 (Forward regener-
ative), 2nd motor
0.0 to 500.0 (%)
(Limited at at torque equivalent to 200% of
inverter ND rating)
150.0 (%)
bA216
-
Torque limit LADSTOP selec-
tion, 2nd-motor
00 (Disabled)/01 (Enabled)
00
bA220
-
Over current suppress enable,
2nd-motor
00 (Disabled)/01 (Enabled)
01
bA221
-
Over current suppress Level,
2nd-motor
(0.0 to 2.0)
× Inverter rated current (A)
*1
*2
bA222
-
Overload restriction 1 mode
selection, 2nd-motor
00 (Disabled)/
01 (Accelerate at constant speed)/
02 (Only constant speed)/
03 (Accelerate at constant speed/Increase speed
at regeneration)
01
bA223
○
Overload restriction 1 active
level, 2nd-motor
(0.2 to 2.0)
× Inverter rated current (A)
*1
*3
bA224
○
Overload restriction 1 action
time, 2nd-motor
0.10 to 3600.00 (s)
1.00
bA226
-
Overload restriction 2 mode
selection, 2nd-motor
00 (Disabled)/
01 (Accelerate at constant speed)/
02 (Only constant speed)/
03 (Accelerate at constant speed/Increase speed
at regeneration)
01
bA227
○
Overload restriction 2 active
level, 2nd-motor
(0.2 to 2.0)
× Inverter rated current (A)
*1
*3
bA228
○
Second overload limit 2 opera-
tion time
0.10 to 3600.00 (s)
1.00
bA240
○
Over-voltage suppression
enable, 2nd-motor
00 (Disabled)/
01 (DC voltage constant deceleration)/
02 (Acceleration only at deceleration)/
03 (Acceleration at constant speed/deceleration)
00
bA241
○
Over-voltage suppression active
level, 2nd-motor
(200 V class) 330.0 to 400.0 (V)
(400 V class) 660.0 to 800.0 (V)
(200 V class) 380.0
(400 V class) 760.0
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial value
Note
Summary of Contents for RX - 2
Page 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Page 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Page 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Page 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Page 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Page 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Page 919: ......